Df1 port x, Port x – ProSoft Technology MVI69-DFCM User Manual

Page 27

Advertising
background image

Configuring the MVI69-DFCM Module

MVI69-DFCM ♦ CompactLogix or MicroLogix Platform

DF1 Interface Module

ProSoft Technology, Inc.

Page 27 of 117

November 3, 2008

2.2.6 Read Register Count

0 to 5000

This parameter specifies the number of registers to be transferred from the
module to the processor. Valid entry for this parameter is 0 to 5000.

2.2.7 Write Register Start

0 to 4999

This parameter specifies the starting register in the module where the data will be
transferred from the processor to the module. Valid range for this parameter is 0
to 4999.

2.2.8 Read Register Count

0 to 5000

This parameter specifies the number of registers to be transferred from the
module to the processor. Valid entry for this parameter is 0 to 5000.

2.3

[DF1 Port x]

The following shows a sample DF1 Port x section of the configuration file.

[DF1 Port x]

Enabled : Yes # Y=Use port, N=Do not use port

RS Interface : 0 # 0=RS-232, 1=RS-485, 2=RS-422

Type : Master # M=Master, S=Slave

Local Station ID : 0 # DF1 node address

Protocol : F # F=Full-Duplex, H=Half-Duplex

Termination Type : CRC # B=BCC, C=CRC

Baud Rate : 19200 # Baud rate for Port 110-38400

Parity : None # N=None,O=Odd,E=Even,M=Mark,S=Space

Data Bits : 8 # 5, 6, 7 or 8

Stop Bits : 1 # 1 or 2

Min Response Delay : 0 # 0-65535 mSec before sending response msg

RTS On : 0 # 0-65536 mSec before message

RTS Off : 1 # 0-65536 mSec after message

Use CTS Line : No # Use CTS modem control line (Y/N)

Response Timeout : 1000 # Response message timeout (0-65535 mSec)

Retry Count : 3 # Response failure retry count

ENQ Delay : 10 # 0-65535 mSec before DLE-ENQ sent

Minimum Command Delay : 10 # Minimum number of msec's between commands

Error Delay Counter : 100 # 0-65535 Command cycle count if error

Command Control Reg : -1 # Cmd control start DB Reg (-1=ignore)

First File : 7 # First file number for SLC simulation

File Size : 200 # Number of elements in each file

File Offset : 0 # Database offset for first file element

Modify each of the parameters as follows based on the needs of your application: