Reference MVI69-DFCM

♦ CompactLogix or MicroLogix Platform

DF1 Interface Module

ProSoft Technology, Inc.

Page 77 of 117

November 3, 2008

Set Module Time Response

Read Block: Set Module Time

Offset Description

Length

0 9972

1

1

Write Block ID

1

2 to (n+1)

Spare

n=60, 120, or 240 depending on what is entered in the Block Transfer Size parameter (refer to the
configuration file).

Get Module Time for Processor Time

Write Block: Get Module Time

Offset Description

Length

0 9973

1

1 to n

Spare

n=60, 120, or 240 depending on what is entered in the Block Transfer Size parameter (refer to the
configuration file).

Read Block: Write Module Time

Offset Description

Length

0 9973

1

1

Write Block ID

1

2

Year (0 to 9999)

1

3

Month (1 to 12)

1

4

Day (1 to 31)

1

5

Hour (0 to 23)

1

6

Minutes (0 to 59)

1

7

Seconds (0 to 59)

1

8 to n

Spare

n=60, 120, or 240 depending on what is entered in the Block Transfer Size parameter (refer to the
configuration file).

Warm Boot

This block is sent from the CompactLogix or MicroLogix processor to the module
(output image) when the module is required to perform a warm-boot (software
reset) operation. The structure of the control block is shown below:

Offset Description

Length

0 9998

1

1 to n

Spare

247

n=60, 120, or 240 depending on what is entered in the Block Transfer Size parameter (refer to the
configuration file).