The LEDs indicate the module's operating status as follows:

Module Color Status

Indication

On

Data is being transferred between the module and a remote
terminal using the Configuration/Debug port.

CFG Green

Off

No data is being transferred on the Configuration/Debug
port.

On

Data is being transferred between the module and the
DFCM network on Port 1.

P1 Green

Off

No data is being transferred on the port.

On

Data is being transferred between the module and the
DFCM network on Port 2.

P2 Green

Off

No data is being transferred on the port.

On

The MVI69-DFCM module program has recognized a
communication error on one of its ports.

APP Amber

Off

The MVI69-DFCM is functioning normally.

On

The LED is on when the module is performing a write
operation on the backplane.

BP ACT

Amber

Off

The LED is off when the module is performing a read
operation on the backplane. Under normal operation, the
LED should blink rapidly on and off.

Off

The card is not receiving any power and is not securely
plugged into the rack.

Green

The module is operating normally.

OK Red/

Green

Red

The program has detected an error or is being configured. If
the LED remains red for over 10 seconds, the program has
probably halted. Remove the card from the rack and re-
insert the card to restart the module's program.

Off

The battery voltage is OK and functioning.

BAT Red

On

The battery voltage is low or battery is not present. Allow
battery to charge by keeping module plugged into rack for
24 hours. If BAT LED still does not go off, contact ProSoft
Technology, as this is not a user serviceable item.

During module configuration, the OK LED will be red and the APP and BP ACT
LEDs will be on.

If the APP, BP ACT and OK LEDs blink at a rate of every one-second, this
indicates a serious problem with the module. Call ProSoft Technology support to
arrange for repairs.