ProSoft Technology MVI69-DFCM User Manual

Page 79

Advertising
background image

Reference MVI69-DFCM

♦ CompactLogix or MicroLogix Platform

DF1 Interface Module

ProSoft Technology, Inc.

Page 79 of 117

November 3, 2008

Step Description

2

A Host device, such as the Rockwell Automation PLC or an HMI application issues a
read or write command to the module's node address. The port driver qualifies the
message before accepting it into the module.

3

After the module accepts the command, the data is immediately transferred to or from
the internal database in the module. If the command is a read command, the data is
read out of the database and a response message is built. If the command is a write
command, the data is written directly into the database and a response message is built.

4

After the data processing has been completed in Step 3, the response is issued to the
originating master node.

5

Counters are available in the Status Block that permit the ladder logic program to
determine the level of activity of the Slave Driver.

Review the Module Set Up section for a complete list of the parameters that
must be defined for a slave port. The slave driver supports the following DFCM
command set:

Basic Command Set Functions

Function
Code

Command Function Definition

PLC5

SLC500 &
MicroLogix

Power-
monitor II

ControlLogix

1 0x00

N/A

Protected

Write

X

X

2 0x01

N/A

Unprotected

Read

X X X

3 0x02

N/A

Protected

Bit

Write

X

X

4

0x05

N/A

Unprotected Bit Write X

X

5 0x08

N/A

Unprotected

Write

X X X

PLC-5 Command Set Functions

Function
Code

Command Function Definition

PLC5

SLC500

&

MicroLogix

Power-
monitor II

ControlLogix

100

0x0F

0x00

Word Range Write
(Binary Address)

X

X

101

0x0F

0x01

Word Range Read
(Binary Address)

X

X

102 0x0F 0x26

Read-Modify-Write

(Binary Address)

X

X

150

0x0F

0x00

Word Range Write

(ASCII Address)

X

X

151

0x0F

0x01

Word Range Read
(ASCII Address)

X

X

152 0x0F 0x26

Read-Modify-Write
(ASCII Address)

X

X

SLC-500 Command Set Functions

Function
Code

Command Function Definition

PLC5

SLC500 &
MicroLogix

Power-
monitor II

ControlLogix

501 0x0F 0xA1

Protected

Typed

Logical Read With

Two Address Fields

X X

502 0x0F 0XA2

Protected

Typed

Logical Read With

Three Address Fields

X X X

509 0x0F 0XA9

Protected

Typed

Logical Write With

Two Address Fields

X X