ProSoft Technology MVI69-DFCM User Manual

Page 93

Advertising
background image

Reference MVI69-DFCM

♦ CompactLogix or MicroLogix Platform

DF1 Interface Module

ProSoft Technology, Inc.

Page 93 of 117

November 3, 2008

5.7.4 Module Specific Error (not DFCM Compliant)

Code (Int)

Code (Hex) Description

-1

0xFFFF

CTS modem control line not set before transmit

-2

0xFFFE

Timeout while transmitting message

-10

0xFFF6

Timeout waiting for DLE-ACK after request

-11

0xFFF5

Timeout waiting for response after request

-12

0xFFF4

Reply data does not match requested byte count

-20

0xFFEC

DLE-NAK received after request

-21

0xFFEB

DLE-NAK sent after response

5.8

DF1 Command Set For ProSoft Technology Communication Modules

5.8.1 Introduction

This document contains a complete description of the command set required to
communicate with DF1 protocol devices using a ProSoft communication module.
ProSoft communication modules that contain a virtual DF1 master device use
this command set to control and monitor data in DF1 protocol devices. These
include Rockwell Automation PLC, SLC, MicroLogix and ControlLogix controllers
and field devices supporting the DF1 protocol. ProSoft supports the DF1 protocol
on both the serial and network interface. The network interface requires the use
of the port service address 0xAF12 as specified in the ControlNet Specification.
Rockwell Automation supports this feature in the ControlLogix 5550, PLC5 xx/E
and SLC 5/05 processors.

The ProSoft modules contain a virtual database that is defined by the user. This
database is used as the source for write commands and the destination for read
commands issued on the virtual DF1 master devices. The module interfaces data
contained in remote DF1 slave devices to the virtual database using the DF1
master. User commands are issued out of the DF1 master from a command list.
These commands gather or control data in the DF1 slave devices. The following
illustration shows the relationships discussed above: