Reference MVI69-DFCM

♦ CompactLogix or MicroLogix Platform

DF1 Interface Module

ProSoft Technology, Inc.

Page 73 of 117

November 3, 2008

Read Block: Read Slave Status

Offset Description

Length

0

3002 to 3006 or 3102 to 3106

1

1

Write Block ID

1

2 to 61

Slave Poll Status Data

60

62 to n

Spare (if present)

The sample ladder logic shows how to override the value in the slave status table
to disable slaves (state value of 3) by sending a special block of data from the
processor to the slave. Port 1 slaves are disabled using block 3000, and Port 2
slaves are disabled using block 3100. Each block contains the slave node
addresses to disable. The structure of the block is displayed below:

Write Block: Disable Slaves

Offset Description

Length

0

3000 or 3100

1

1

Number of slaves in block

1

2 to 61

Slave indexes

60

62 to (n+1)

Spare

n=120, or 240 (if configured)

The module will respond with a block with the same identification code received
and indicate the number of slaves acted on with the block. The format of this
response block is displayed below:

Read Block: Disable Slaves

Offset Description

Length

0

3000 or 3100

1

1

Write Block ID

1

2

Number of slaves processed

1

3 to (n+1)

Spare

n=60, 120, or 240 (if configured)

The sample ladder logic explains how to override the value in the slave status
table to enable the slave (state value of 1) by sending a special block. Port 1
slaves are enabled using block 3001, and Port 2 slaves are enabled using block
3101. Each block contains the slave node addresses to enable. The format of the
block is displayed below:

Write Block: Enable Slaves

Offset Description

Length

0

3001 or 3101

1

1

Number of slaves in block

1

2 Slave

indexes

1

3 to n

Spare

n=60, 120, or 240 depending on what is entered in the Block Transfer Size parameter (refer to the
configuration file).