MVI56E-GSC ♦ CompactLogix or MicroLogix Platform

Reference

Enhanced Generic ASCII Serial Communication Module

User Manual

ProSoft Technology, Inc.

Page 131 of 140

May 9, 2014

4.9

Error/Configuration Word

If the module is configured correctly, the configuration error word should have a
value of zero. Any other value indicates a configuration error. Use the value in
the configuration error word to determine which set of parameters are invalid in
the driver configuration area. The following table lists the bits associated with
each configuration error in the word:

Bit

Code

Description

0

0x0001

Invalid Cfg_type

1

0x0002

Invalid Cfg_Baud

2

0x0004

Invalid Cfg_Parity

3

0x0008

Invalid Cfg_DataBits

4

0x0010

Invalid Cfg_StopBits

5

0x0020

Invalid Cfg_Handshake

6

0x0040

Invalid Cfg_RTermcount

7

0x0080

Invalid Cfg_RPacketLen

8

0x0100

Invalid Cfg_RTimeout

9

0x0200

Invalid Cfg_RDelay

10

0x0400

Invalid Cfg_WTimeout

11

0x0800

Invalid Resv_Bit11

12

0x1000

Invalid Resv_Bit12

13

0x2000

Invalid Resv_Bit13

14

0x4000

Invalid Resv_Bit14

15

0x8000

Invalid Err_ROverflow

4.10 Cable Connections

The application ports on the MVI56E-GSC module support RS-232, RS-422, and
RS-485 interfaces. Please inspect the module to ensure that the jumpers are set
correctly to correspond with the type of interface you are using.

Note: When using RS-232 with radio modem applications, some radios or modems require

hardware handshaking (control and monitoring of modem signal lines). Enable this in the
configuration of the module by setting the UseCTS parameter to 1.

4.10.1 Ethernet Cable Specifications

The recommended cable is Category 5 or better. A Category 5 cable has four
twisted pairs of wires, which are color-coded and cannot be swapped. The
module uses only two of the four pairs.