Specification

Description

Backplane Current Load

800 mA @ 5 Vdc
3 mA @ 24 Vdc

Operating Temperature

0°C to 60°C (32°F to 140°F)

Storage Temperature

-40°C to 85°C (-40°F to 185°F)

Shock

30 g operational
50 g non-operational
Vibration: 5 g from 10 to 150 Hz

Relative Humidity

5% to 95% (without condensation)

LED Indicators

Battery Status (ERR)
Application Status (APP)
Module Status (OK)

4-Character, Scrolling, Alpha-
Numeric LED Display

Shows Module, Version, IP, Port Status, P1 and
P2 Settings, and Error Information

Debug/Configuration Ethernet port (E1 - Config)

Ethernet Port

10/100 Base-T, RJ45 Connector, for CAT5 cable
Link and Activity LED indicators
Auto-crossover cable detection

Serial Application ports (P1 & P2)

Software configurable
communication parameters

Baud rate: 110 baud to 115.2 kbps
RS-232, RS-485, and RS-422
Parity: none, odd or even
Data bits: 5, 6, 7, or 8
Stop bits: 1 or 2
RTS on/off delay: 0 to 65535 milliseconds
Full hardware handshaking control (optional)
Radio and modem support

App Ports (P1, P2)

RJ45 (DB-9M with supplied adapter cable)
Configurable RS-232 hardware handshaking
500V Optical isolation from backplane
RS-232, RS-422, RS-485 jumper-select, per port
RX (Receive) and TX (Transmit) LEDs, each port

Shipped with Unit

RJ45 to DB-9M cables for each serial port
5 foot Ethernet Straight-Thru Cable (Gray)

4.2

General Concepts

The following discussion explains several concepts that are important for
understanding module operation.