MVI56E-GSC ♦ CompactLogix or MicroLogix Platform

Start Here

Enhanced Generic ASCII Serial Communication Module

User Manual

ProSoft Technology, Inc.

Page 37 of 140

May 9, 2014

This action opens the S

ELECT

M

ODULE

dialog box.

2 Select the 1756-M

ODULE

(G

ENERIC

1756

M

ODULE

)

from the list and click OK.

This action opens the N

EW

M

ODULE

dialog box.

3 Set the Module Properties values as follows:

Parameter

Value

Name

Enter a module identification string. Example: GSC

Description

Enter a description for the module. Example: Enhanced
Generic ASCII Serial Communication Module.

Comm Format

Select DATA-SINT.

Slot

Enter the slot number in the rack where the MVI56E-GSC
module is located.

Input Assembly Instance

1

Input Size

500

Output Assembly Instance

2