Reference

MVI56E-GSC ♦ CompactLogix or MicroLogix Platform

User Manual

Enhanced Generic ASCII Serial Communication Module

Page 84 of 140

ProSoft Technology, Inc.

May 9, 2014

4.2.3 Termination of Received Data

When data is received on either of the application ports, you must define in the
configuration when this data will be transferred to the ControlLogix processor.
Within the module, this is known as the termination type for port. When the
termination condition is met, the data will be sent from the port’s receive buffer
(data area of 4096 bytes) to the processor using the input image. This
termination type is set using a bit-mapped value, entered into the
GSC.CONFIG.P

ORT

X.T

YPE

field of the configuration controller tags.

Termination Mode Selection Chart

0 = No Bits

Set

1 = Bit 0 Set

2 = Bit 1 Set

4 = Bit 2 Set

8 = Bit 3 Set

Decimal
Value of

Bits

Selected

(S)

Streaming

Mode

Selected

(T)

Terminating

Characters

Selected

(M)

Message

Timeout

Selected

(D)

Intercharacter

Delay

Selected

(P)

Packet Length

Selected

Port Types

Selected by

Bitmap

0

0

S

1

1

T

2

2

M