Using prosoft configuration builder software – ProSoft Technology MVI56E-GSC/ GSCXT User Manual

Page 16

Advertising
background image

Start Here

MVI56E-GSC ♦ CompactLogix or MicroLogix Platform

User Manual

Enhanced Generic ASCII Serial Communication Module

Page 16 of 140

ProSoft Technology, Inc.

May 9, 2014

Warning: When you insert or remove the module while backplane power is on, an electrical arc

can occur. An electrical arc can cause personal injury or property damage by sending an

erroneous signal to the system’s actuators. This can cause unintended machine motion or loss of
process control. Electrical arcs may also cause an explosion when they happen in a hazardous

environment. Verify that power is removed or the area is non-hazardous before proceeding.

Repeated electrical arcing causes excessive wear to contacts on both the module and its mating

connector. Worn contacts may create electrical resistance that can affect module operation.

1 Align the module with the top and bottom guides, and then slide it into the

rack until the module is firmly against the backplane connector.

2 With a firm, steady push, snap the module into place.
3 Check that the holding clips on the top and bottom of the module are securely

in the locking holes of the rack.

4 Make a note of the slot location. You must identify the slot in which the

module is installed in order for the sample program to work correctly. Slot
numbers are identified on the green circuit board (backplane) of the
ControlLogix rack.

5 Turn power ON.

Note: If you insert the module improperly, the system may stop working or may behave

unpredictably.

1.8

Using ProSoft Configuration Builder Software

ProSoft Configuration Builder (PCB) provides a quick and easy way to manage
module configuration files customized to meet your application needs. PCB is not
only a powerful solution for new configuration files, but also allows you to import
information from previously installed (known working) configurations to new
projects.

Advertising