Start Here

MVI56E-GSC ♦ CompactLogix or MicroLogix Platform

User Manual

Enhanced Generic ASCII Serial Communication Module

Page 42 of 140

ProSoft Technology, Inc.

May 9, 2014

2 Select 1756-MODULE

3 Set the Module Properties values as follows:

Parameter

Value

Name

Enter a module identification string. Example: GSC_2.

Description

Enter a description for the module. Example: ProSoft
Enhanced Generic ASCII Serial Communication Module.

Comm Format

Select DATA-SINT.

Slot

Enter the slot number in the rack where the MVI56E-GSC
module is located.

Input Assembly Instance

1

Input Size

500

Output Assembly Instance

2

Output Size

496

Configuration Assembly Instance

4

Configuration Size

0

4 Click OK

to confirm. The new module is now visible:

5 Expand the T

ASKS

folder, and then expand the M

AIN

T

ASK

folder.

6 On the M

AIN

P

ROGRAM

folder, click the right mouse button to open a shortcut

menu. On the shortcut menu, choose N

EW

R

OUTINE

. As an alternative to

creating a separate New Routine, you could skip to Step 8 and import the
AOI for the second module into the same routine you created for the first
module.