Page 59

MVI56E-GSC ♦ CompactLogix or MicroLogix Platform
MVI56E-GSC Configuration
Enhanced Generic ASCII Serial Communication Module
User Manual
ProSoft Technology, Inc.
Page 59 of 140
May 9, 2014
2.2.20 Port[x].WMinDelay
This parameter specifies the minimum number of milliseconds to delay before
transmitting a message out the port. This pre-send delay is applied before the
RTS On time. This may be required when communicating with slow devices. Use
this parameter if you set the P
ORT
[X].T
YPE
Port[x].Type (page 54) to 8, 9, 10, 11,
12, 13, 14, or 15.
2.3
Changing parameters during operation
When you change the configuration parameters in RSLogix, you must reboot or
cycle power to the module off and on before the new configuration takes effect.
You may also change the value of the GSC.ColdBoot or GSC.WarmBoot
controller tags from 0 to 1 to reboot the module from logic.