MVI56E-GSC ♦ CompactLogix or MicroLogix Platform

Diagnostics and Troubleshooting

Enhanced Generic ASCII Serial Communication Module

User Manual

ProSoft Technology, Inc.

Page 75 of 140

May 9, 2014

3.11 Troubleshooting

Use the following troubleshooting steps if you encounter problems when the
module is powered up. If these steps do not resolve your problem, please contact
ProSoft Technology Technical Support.

Processor Errors

Problem Description

Steps to take

Processor Fault

Verify that the module is plugged into the slot that has been configured
for the module in the I/O Configuration of RSLogix.
Verify that the slot location in the rack has been configured correctly in
the ladder logic.

Processor I/O LED
flashes

This indicates a problem with backplane communications. A problem
could exist between the processor and any installed I/O module, not just
the MVI56E-GSC. Verify that all modules in the rack are correctly
configured in the ladder logic.

Module Errors

Problem Description

Steps to take

MVI56E modules with
scrolling LED display:
<Backplane Status>
condition reads ERR

This indicates that backplane transfer operations are failing. Connect to
the module’s Configuration/Debug port to check this.
To establish backplane communications, verify the following items:

The processor is in RUN or REM RUN mode.

The backplane driver is loaded in the module.

The module is configured for read and write data block transfer.

The ladder logic handles all read and write block situations.

The module is properly configured in the processor I/O configuration
and ladder logic.

OK LED remains RED

The program has halted or a critical error has occurred. Connect to the
Configuration/Debug port to see if the module is running. If the program
has halted, turn off power to the rack, remove the card from the rack and
re-insert the card in the rack, and then restore power to the rack.