MVI56E-GSC ♦ CompactLogix or MicroLogix Platform

User Manual

Enhanced Generic ASCII Serial Communication Module

Page 28 of 140

ProSoft Technology, Inc.

May 9, 2014

 If the MVI56E-GSC module is located in the same rack as the first 1756-

ENBT module, select

R

ACK

N

O

.

1 and configure the associated parameters.

 If the MVI56E-GSC is available in a remote rack (accessible through

ControlNet or Ethernet/IP), include all racks (by using the A

DD

R

ACK

button).

Parameter

Description

Source Module

Source module type. This field is automatically selected
depending on the destination module of the last rack (1756-
CNB or 1756-ENBT).

Source Module IP Address

IP address of the source module (only applicable for 1756-
ENBT)

Source Module Node Address

Node address of the source module (only applicable for 1756-
CNB)

Destination Module

Select the destination module associated to the source module
in the rack. The connection between the source and destination
modules is performed through the backplane.

Destination Module Slot Number

The slot number where the destination MVI56E module is
located.

To use the CIPconnect Path Editor, follow these steps.

1 Configure the path between the 1756-ENBT connected to your PC and the

MVI56E-GSC module.

o

If the module is located in a remote rack, add more racks to configure the
full path.

o

The path can only contain ControlNet or Ethernet/IP networks.

o

The maximum number of supported racks is six.

2 Click C

ONSTRUCT

CIP

P

ATH

to build the path in text format

3 Click OK

to confirm the configured path.

The following examples should provide a better understanding on how to set up
the path for your network.

Example 1: Local Rack Application
For this example the MVI56E-GSC module is located in the same rack as the
1756-ENBT that is connected to the PC.

Ethernet

Rack 1

MVI56E Module

1756-ENBT

0

1

2

3