4.1.2 Ethernet LED Indicators

The Ethernet LEDs indicate the module's Ethernet port status as follows:

LED

State

Description

Data

OFF

Ethernet connected at 10Mbps duplex speed

AMBER Solid Ethernet connected at 100Mbps duplex speed

Link

OFF

No physical network connection is detected. No Ethernet
communication is possible. Check wiring and cables.

GREEN Solid
or Blinking

Physical network connection detected. This LED must be ON solid
for Ethernet communication to be possible.

4.1.3 Non-Scrolling LED Status Indicators

The non-

scrolling LEDs indicate the module’s operating status as follows:

LED Label

Color

Status

Indication

APP

Red or
Green

OFF

The module is not receiving adequate power or is not securely
plugged into the rack. May also be OFF during configuration
download.

GREEN

The MVI56E-SIE is working normally.

RED

The most common cause is that the module has detected a
communication error during operation of an application port.
The following conditions may also cause a RED LED:

The firmware is initializing during startup

The firmware detects an on-board hardware problem
during startup

Failure of application port hardware during startup

The module is shutting down

The module is rebooting due to a ColdBoot or WarmBoot
request from the ladder logic or Debug Menu

OK

Red or
Green

OFF

The module is not receiving adequate power or is not securely
plugged into the rack.

GREEN

The module is operating normally.

RED

The module has detected an internal error or is being
initialized. If the LED remains RED for over 10 seconds, the
module is not working. Remove it from the rack and re-insert it
to restart its internal program.

ERR

Red

OFF

The battery voltage is OK and functioning.

ON

The battery voltage is low or battery is not present. Allow
battery to charge by keeping module plugged into rack for 24
hours. If ERR LED still does not go off, contact ProSoft
Technology, as the battery is not a user-serviceable item.