ProSoft Technology MVI56E-SIE User Manual

Page 21

Advertising
background image

MVI56E-SIE ♦ ControlLogix Platform

Start Here

Client Communication Module

User Manual

ProSoft Technology, Inc.

Page 21 of 168

September 6, 2012

3 In the New Module dialog box, enter the following values.

Parameter

Value

Name

Enter a module identification string. Example: SIE

Description

Enter a description for the module. Example: S

IEMENS

I

NDUSTRIAL

E

THERNET

C

LIENT

C

OMMUNICATION

M

ODULE

Comm Format

Select D

ATA

-INT.

Slot

Enter the slot number in the rack where the MVI56E-SIE
module is located.

Input Assembly Instance

1

Input Size

250

Output Assembly Instance

2

Output Size

248

Configuration Assembly Instance

4

Configuration Size

0

Important: The Comm Format D

ATA

INTmust be selected in the dialog box,

otherwise the module will not communicate over the backplane of the
ControlLogix rack.

4 Click OK

to continue.

5 Edit the Module Properties. Select the Requested Packet Interval value for

scanning the I/O on the module. This value represents the minimum
frequency at which the module will handle scheduled events. This value
should not be set to less than 1 millisecond. The default value is 5
milliseconds. Values between 1 and 10 milliseconds should work with most
applications.

6 Save the module.