Sie client specific error codes, Command list entry error codes – ProSoft Technology MVI56E-SIE User Manual

Page 132

Advertising
background image

Diagnostics and Troubleshooting

MVI56E-SIE ♦ ControlLogix Platform

User Manual

Client Communication Module

Page 132 of 168

ProSoft Technology, Inc.

September 6, 2012

Decimal

Hex

Description

-11772

0xd204

No linked block in storage medium

-11771

0xd205

Object already exists

-11770

0xd206

Object already exists

-11769

0xd207

Block exists in EPROM

-11767

0xd209

Block does not exist/could not be found

-11762

0xd20e

No block present

-11760

0xd210

Block number too big

-11712

0xd240

Coordination rules were violated

-11711

0xd241

Operation not permitted in current protection level

-11710

0xd242

Protection violation while processing F-blocks. F-blocks can only be
processed after password input

-11263

0xd401

Invalid SZL ID

-11262

0xd402

Invalid SZL index

-11258

0xd406

Diagnosis: Info not available

-11255

0xd409

Diagnosis: DP error

-9215

0xdc01

Invalid BCD code or Invalid time format

SIE Client Specific Error Codes

Decimal

Hex

Description

-33

0xffdf

Failed to connect to server specified in command

-34

0xffde

Failed to create a socket

-36

0xffdc

SIE command response timeout (same as -11)

-37

0xffdb

TCP/IP connection ended before session finished

Command List Entry Error Codes

Decimal

Hex

Description

-40

0xffd8

Too few parameters

-41

0xffd7

Invalid enable code

-42

0xffd6

Internal address > maximum address

-44

0xffd4

Count parameter set to 0

-45

0xffd3

Invalid function code

-46

0xffd2

Invalid swap code

-47

0xffd1

Invalid TSAP code

Advertising