14 Add a copy instruction to the MainRoutine ladder to copy the 10 words from

SIE.DATA.ReadData into the REALDATA array created in the previous step.

Note: The length in the COP instruction is the length of the destination. Since 10 INTs (words)

become 5 REALS (floating-point numbers), the copy length is 5.


15 Verify that the data transferred from S7-300 processor appears correctly in

the REALDATA[0] through REALDATA[4] controller tags.