2 functional specifications, 3 hardware specifications – ProSoft Technology MVI56E-SIE User Manual

Page 135

Advertising
background image

MVI56E-SIE ♦ ControlLogix Platform

Reference

Client Communication Module

User Manual

ProSoft Technology, Inc.

Page 135 of 168

September 6, 2012

5.1.2 Functional Specifications

 Siemens Industrial Ethernet data types overlap in the module's memory

database, so the same data can be conveniently read or written as bit-level or
register-level data.

 Configurable floating-point data movement is supported
 Configurable parameters for the Client including a minimum response delay

of 0 to 65535 ms

 Supports up to 20 Clients with up to 16 commands for each Client
 Error codes, counters, and module status available from module memory

through the Clients, or through the ladder logic and controller tags in
RSLogix 5000

5.1.3 Hardware Specifications

Specification

Description

Dimensions

Standard 1756 ControlLogix

®

single-slot module

Backplane current load

800 mA @ 5 Vdc
3 mA @ 24 Vdc

Operating temperature

0°C to 60°C (32°F to 140°F)

Storage temperature

-40°C to 85°C (-40°F to 185°F)

Shock

30 g operational
50 g non-operational

Vibration

5 g from 10 Hz to 150 Hz

Relative humidity

5% to 95% (with no condensation)

LED indicators

Battery Status (ERR)
Application Status (APP)
Module Status (OK)

4-character, scrolling, alphanumeric
LED display

Shows module, version, IP, application port setting, port
status, and error information

Ethernet port

10/100 Base-T, RJ45 Connector, for CAT5 cable
Link and Activity LED indicators
Auto-crossover cable detection

Cable

5-foot Ethernet straight-through cable (shipped with unit)