Internal Address

0 to 65535 (for bit-level addressing) or

0 to 4999 (for word-level addressing)

This parameter specifies the database address in the module's internal database
to use as the destination for data brought in by a read command or as the source
for data to be sent out by a write command. The database address is interpreted
as a bit address or a 16-bit word (register) address, depending on the Siemens
Industrial Ethernet

’s Data Type used in the command. If Data Type – Bool is

used in the command list, then the database address will be interpreted as a bit
address. When any other data types are used, then the database address is
interpreted as 16-bit word (register) address.

Poll Interval

0 to 65535

This parameter specifies the minimum interval between issuances of a command
during continuous command execution (Enable code of 1). The parameter is
entered in tenths of a second. Therefore, if a value of 100 is entered for a
command, the command executes no more frequently than every 10 seconds.

Reg Count

Regs: This Count will depend on the Siemens processor type

Coils: This Count will depend on the Siemens processor type

Below are the tables of the max reg count limit for three of the Siemens
processors:

CPU315-2

DP

Data Block:

Address Type

Function

Data Type

Max Reg Cnt

Max Reg Cnt

DB

READ

BOOL

1

Write

BOOL

1

READ

BYTE

164

Write

BYTE

164

READ

DINT

41

Write

DINT

41

READ

REAL

41

Write

REAL

41

READ

INT

82

Write

INT

82

READ

TIME

82

Write

TIME

41

READ

COUNT

82

Write

COUNT

82