Framing and Clearances

A. Selecting Fireplace Location

Several options are available to you when choosing a loca-

tion for your fireplace. This fireplace may be used as a room

divider, installed along a wall, across a corner or used in an

exterior chase. See Figure 10.1.
Locating the fireplace in a basement, near frequently opened

doors, central heat outlets or returns, or other locations

Figure 10.1 Fireplace Locations

Fire Risk
Provide adequate clearances.

• Around air openings

• To combustibles

• For service access.
Locate fireplace away from traffic areas.

WARNING

Note:

Illustrations and photos reflect typical installations and

are FOR DESIGN PURPOSES ONLY.

Illustrations/diagrams are not drawn to scale.

Actual installation/appearance may vary due to individual

design preference.

Hearth & Home Technologies reserves the right to alter

its products.

of considerable air movement can affect the performance

and cause intermittent smoke spillage from the front of the

fireplace when no outside air is used. Outside air must be

used for combustion. The Constitution comes equipped with

an outside air inlet to feed combustion air from outside the

home, along with an outside air termination cap. Consider-

ation should be given to these factors before deciding on a

location. See Sections 2 and 10.

Model:

Constitution

(Dimensions for

finished walls)

A

B

C

D

E

F

G

H

I

in.

41-7/8 16 89-1/2 63-5/16 22-7/16 44-3/4 14-1/16 55-15/16 50-7/8

mm

1063 406

2273

1608

570

1137

357

1421

1292

D

C

A

E

F

A

H

G

B

A

B

B

A

I

In an exterior chase

or projecting into a

garage

Across a corner

Along a wall

As a

room

divider

24 in.

(610mm)

24 in.

(610mm)

24 in.

(610mm)

48 in.

(1219mm)

Note: A minimum 1 in. air clearance must be maintained at the back

and to the sides of the fireplace assembly.
Chimney sections at any level require a 2 in. minimum air

space clearance between the framing and chimney sections.

Note: In addition to these framing dimensions, also reference the

following sections:

Clearances (Section 3.B.)

Mantel (Section 8.F.)

Fireplace Dimensions (Section 12.A.)