Warning, D. electrical access and wiring diagram – Hearth and Home Technologies C-40 User Manual

Page 13

Advertising
background image

November 11, 2008

Heatilator • Constitution EPA Fireplace • 480-1091C

Page 13

Fire Risk

Do not apply combustible finishing materials

over any part of the front of this fireplace.

• The metal fireplace face may only be

covered with noncombustible materials

such as ceramic tile, brick, or stone.

• Do not cover or block any cooling air

slots.

The decorative fascia must be removable

for future serviceability of the Automatic

Combustion Control.

WARNING

Fire Risk

Comply with all minimum clearances speci-

fied.

• A minimum 1/2 in. (13mm) air clearance

must be maintained at the back and 1

in. (25mm) to the sides of the fireplace

assembly.

• Chimney sections at any level require a 2

in. (51mm) minimum air space clearance

between the framing and chimney section.

WARNING

D. Electrical Access and Wiring Diagram

NOTE: The manual override switch, rheostat

speed control and cover plate are supplied. You

will need to supply: 14-3 wire with ground; 14-2

wire with ground; standard wall mount junction

box; wire nuts.

1. Remove junction box cover plate on the

bottom right side of the fireplace.

2. Thread the 14-3 with ground wire through

the opening with the strain relief on the cover

plate.

3. Match colors to wire harness, (red to red,

white to white, etc) and secure with wire

nuts.

NOTE: Wiring for fans must be done before

framed enclosure is completed. If using a

Heat Zone kit, it also must be installed before

enclosure is complete.

Figure 13.2 Fan Wiring Diagram

14-2 w/ground

Standard wall mount with

Junction Box

14-3 w/ground

WIRE NUT

WHITE

GREEN

BLACK

BLACK

RED

WHITE

Match colors to wire

harness (red to red,

white to white, etc) and

secure with a wire nut

Incoming Power

(110V)

Power to the Fireplace

Snap Disc

bypass switch

Suggestions:
1. Insulate chase.
2. Finish chase walls with dry wall 5/8 in. (16mm) Type X

face tape.
3. All dimensions are to finished walls and ceilings.

Figure 13.1 Sheetrocked Chase

Fire Risk

• Maintain clearances.

• Use only non-combustible material below

standoffs, material such as cement board

is acceptable.

WARNING

• Framing or finishing material used on the front

of, or in front of, the appliance closer than the

minimums listed, must be constructed entirely of

noncombustible materials (i.e., steel studs, concrete

board, etc.).

Advertising