Heatilator • Constitution EPA Fireplace • 480-1091C

Page 25

Slanted Roofs

Flat Roofs

Chimney must

extend 3 ft

(914 mm)

above the roof

Chimney must extend 2 ft (610 mm)

above any portion of the roof

within 10 ft (3048 mm) of the chimney

Chimney must

extend 3 ft

(914 mm)

above the roof

Chimney must extend 2 ft (610 mm)

above any portion of the roof

within 10 ft (3048 mm) of the chimney

Figure 25.1 Termination Requirements

Figure 25.2 Multiple Chimneys

6

Complete the Enclosure

A. Chimney Termination (2-10-3 Rule)

Chimney Termination Requirements (See Figures 25.1 and 25.2)

• Must have a cap approved and listed for this fireplace system

• Must not be located where it will become plugged by snow or other material

• Must terminate at least 3 ft (914 mm) above the roof

and at least 2 ft (610 mm) above any portion of the roof within 10 ft

(3.05 m)

• Must be located away from trees or other structures

Gas

Termination

Wood & Fuel Oil

Termination

Comments

A

6 in.

20 in. min.

Horizontal distance between terminations

B

20 in.

24 in. min.

Distance to perpendicular wall

C

18 in.

18 in.

Vertical distance between terminations

C

A

GAS

TERMINATION

B

GAS, WOOD OR FUEL

OIL TERMINATION