Warning, Caution – Hearth and Home Technologies C-40 User Manual

Page 17

Advertising
background image

November 11, 2008

Heatilator • Constitution EPA Fireplace • 480-1091C

Page 17

Figure 17.1 Outside Combustion Air Placement

Outlet blocked by

snow, leaves, etc.

NO

Garage or

combustible

liquids storage

NO

Attic space

NO

Outlet placed

higher than 3 ft

below the

termination cap

NO

Use only duct materials

specified by manufacturer

Note: When elevating the fireplace above the hearth

extension the front of the elevated platform must be

protected with a protective metal hearth strip (not included)

as shown in Figure 18.2.

• Place the Protective Metal Hearth Strips

Included with your fireplace you will find two metal

hearth strips measuring approximately 23 in. x 4 in.

(584 mm x 102 mm). These strips are used to provide

added protection where the fireplace and the hearth ex-

tension meet.
Slide each metal strip 2 in. (51 mm) under the front edge

of the fireplace. The individual pieces must overlap each

other by 1 in. (25 mm) minimum in the middle of the fire-

place to provide continuous coverage of the floor. See

Figure 18.1. These metal strips should extend from the

front and sides of the fireplace opening by 2 in. (51 mm).

Screw metal strips in place.

Fire Risk!

• Prevent contact with sagging, loose

insulation.

• Do NOT install against vapor barriers or

exposed insulation.

WARNING

Fire Risk!

• Metal hearth strips MUST be installed.
Sparks or embers may ignite flooring.

WARNING

B. Secure the Fireplace

• Position the Fireplace

This fireplace may be placed on either a combustible or

noncombustible continuous flat surface. Follow the in-

structions for framing in Section 3.C. Slide the fireplace

into position. Be sure to provide the minimum 1 in. air

clearance at the sides and at back of the fireplace as-

sembly. See Section 3.B.

CAUTION

Sharp Edges
• Wear protective gloves

and safety glasses during

installation.

Advertising