Finishing, Warning, A. hearth extension – Hearth and Home Technologies C-40 User Manual

Page 38

Advertising
background image

Page 38

Heatilator • Constitution EPA Fireplace • 480-1091C

November 11, 2008

8

Finishing

A. Hearth Extension

A hearth extension must be installed with all fireplaces to

protect the combustible floor in front of the fireplace from

both radiant heat and sparks. See Figures 38.1 below, and

Figures 40.1 and 40.2 on page 40.

2 in. (51 mm)

required

High temperature

(300°F min.) continuous,

non-combustible sealant

Tile, stone or other

non-combustible material

Floor constructed of wood or

other combustible material

HX3 or HX4

Hearth Ext

or equivalent

insulation

(see Table below)

Fireplace

Protective

Metal Hearth

Strip

Figure 38.1 Hearth Extension Construction

Table 38.2

B. Calculating Alternate Floor Protection

Material

Thermal Conductivity: k value
The k value indicates the amount of heat (in BTU’s) that will flow

in 1 hour through 1 square foot of a uniform material 1 inch thick

for each degree (F) of temperature difference from one side of

the material to the other. The LOWER the k factor means less

heat is being conducted through the non-combustible material

to the combustible material beneath it. The k value of a mate-

rial must be equal or smaller then the required k value to be

acceptable.

(BTU) (inch)

(foot

2

(hour) (

o

F)

Thermal Resistance: R value
The R value is a measure of a material’s resistance to

heat transfer. R value is convenient when more than one

material is used since you can add the R values together,

whereas you can not do this for k value. The HIGHER the R

factor means less heat is being conducted through the non-

combustible material to the combustible material beneath it.

The R value of a material must be equal or larger then the

required R value to be acceptable.
Converting k to R:
Divide 1 by k and multiply the results times the thickness in inch-

es of the material.

R = 1/k x inches of thickness

Converting R to k:
Divide the inches of thickness by R.

k = inches of thickness/R

Calculations:
Example: Floor protection requires k value of 0.84 and 3/4 inch

thick.
Alternative material has a k value of 0.6 and is 3/4 inch thick.
Divide 0.6 by .75 = k value of 0.80. This k value is smaller than

0.84 and therefore is acceptable.

Fire Risk

• Maintain clearances.

• Use only non-combustible material below

standoffs, material such as cement board

is acceptable.

WARNING

• Framing or finishing material used on the front

of, or in front of, the appliance closer than the

minimums listed, must be constructed entirely of

noncombustible materials (i.e., steel studs, concrete

board, etc.).

Hearth Extension Insulation Alternatives

Minimum R Value = 2.18

Material

k per inch

thick

R per inch

thick

Minimum

thickness

required

Hearth & Home HX3, HX4

0.49

2.18

1 in.

USG Micore 300™

0.49

2.18

1 in.

USG Durock™ Cement Board

1.92

0.52

2-1/4 in.

Cement Mortor

5.0

0.20

5-7/8 in.

Common Brick

5.0

0.20

5-7/8 in.

Ceramic Tile

12.50

0.08

14-5/8 in.

Armstrong™ Privacy

Guard Plus

0.46

2.18

1/2 in.

Marble

14.3-20.0 0.07-0.05 16-5/8 in. - 23-3/8 in.

Advertising