Warning, A. chimney requirements, Table 20.2 – Hearth and Home Technologies C-40 User Manual

Page 20: B. chimney termination requirements

Advertising
background image

Page 20

Heatilator • Constitution EPA Fireplace • 480-1091C

November 11, 2008

A. Chimney Requirements

Vertical distances are measured from the base of the fire-

place as shown in Figure 20.1.

To determine the chimney components needed to complete

your particular installation, follow the steps below:
• Determine the total vertical height of the fireplace

installation. This dimension is measured from the base of

the fireplace assembly to the point where the smoke exits

the termination cap.

• Subtract the effective height of the fireplace assembly from

the overall height of the fireplace installation (measured

from the base of the fireplace to the bottom of the

termination cap, 13 ft. (4m).

• Refer to Table 20.2 to determine what components must

be selected to complete the fireplace installation.

• Determine the number of ceiling firestops, stabilizers,

roof flashing, etc. required to complete the fireplace

installation.

6 ft (1.8 m) max.

unsupported

run

20 ft (6.10 m) max.

pipe between an

offset & return

Ceiling firestop

35 ft (10.7 m)

max. straight

unsupported

chimney height

14.5 ft (4.42 m) min. height/single offset-return

20 ft. (6.10 m) min. height/double offset-return

50 ft (15.24 m) max. height

6 ft (1.83 m) max.

unsupported chimney

above roof

44 in.

(1118 mm)

to top of

standoffs

Figure 20.1 Chimney Requirements

Table 20.2

Fire Risk

• Must maintain 2 in. (51 mm) air clearance

to insulation and other combustible

materials.

WARNING

HEIGHT OF CHIMNEY COMPONENTS

in.

mm

Chimney Stabilizer

SL3

4-3/4

121

Ceiling Firestops

FS338

0

0

FS339

0

0

FS340

0

0

Offsets/Returns

SL315

13-3/8

340

SL330

15-1/2

394

Roof Flashing

RF370

0

0

RF371

0

0

Chimney Sections*

SL306

4-3/4

121

SL312

10-3/4

273

SL318

16-3/4

425

SL324

22-3/4

578

SL336

34-3/4

883

SL348

46-3/4

1187

* Dimensions reflect effective height.

Note: A maximum of two pairs of offsets and returns may

be used.

B. Chimney Termination Requirements

Minimum overall straight height

13 ft

3.96 m

Minimum height with single offset/

return

14.5 ft

4.42 m

Double offset/return minimum height

20 ft

6.1 m

Maximum height

50 ft

15.24 m

Maximum chimney length between an

offset and return

20 ft

6.1 m

Maximum distance between chimney

stabilizers

35 ft

10.67 m

Maximum unsupported chimney

length between the offset and return

6 ft

1.83 m

Maximum unsupported chimney

height above the fireplace

35 ft

10.67 m

Maximum unsupported chimney

above roof

6 ft

1.83 m

WARNING

• Do NOT connect this unit to a chimney flue

servicing another appliance.

• Do NOT connect to any air distribution duct or

system.

May allow flue gases to enter the house.

Asphyxiation Risk.

Advertising