HP MSL6000 Series User Manual

Page 119

Advertising
background image

MSL6000 series tape library user guide 119

307A

Diag get drive 2 status failed
(Failed to get drive status, communication

error.)

•

Press the Enter button to reboot.

•

Ensure the drive shows good status

through the drive status window.

•

Deactivate the drive using the GUI control

panel maintenance menu.

•

Reseat drive.

•

Check cabling.

•

Load/unload a cartridge to the drive to

verify.

•

Check the tape cartridge used in the last

operation for damage.

•

Run the cartridge cycle diagnostic to

verify.

307B

Diag get drive 3 status failed
(Failed to get drive status, communication

error.)

•

Press the Enter button to reboot.

•

Ensure the drive shows good status

through the drive status window.

•

Deactivate the drive using the GUI control

panel maintenance menu.

•

Reseat drive.

•

Check cabling.

•

Load/unload a cartridge to the drive to

verify.

•

Check the tape cartridge used in the last

operation for damage.

•

Run the cartridge cycle diagnostic to

verify.

3082

Drive Stow Failed, Media Returned to

Source

•

Press the Enter button to clear the

message.

•

Use only media approved for the drive

type.

•

Invalid user initiated operation. Set

parameters correctly and try again.

3083

Drive Stow Failed, Media Remains in

Drive

•

Press the Enter button to clear the

message.

•

Invalid user initiated operation. Set

parameters correctly and try again.

•

Ensure cartridges are in magazines.

Table 10

Fault Symptom Codes (continued)

FSC

Message

ERP