HP MSL6000 Series User Manual

Page 119

Advertising
background image

MSL6000 series tape library user guide 119

307A

Diag get drive 2 status failed
(Failed to get drive status, communication

error.)

Press the Enter button to reboot.

Ensure the drive shows good status

through the drive status window.

Deactivate the drive using the GUI control

panel maintenance menu.

Reseat drive.

Check cabling.

Load/unload a cartridge to the drive to

verify.

Check the tape cartridge used in the last

operation for damage.

Run the cartridge cycle diagnostic to

verify.

307B

Diag get drive 3 status failed
(Failed to get drive status, communication

error.)

Press the Enter button to reboot.

Ensure the drive shows good status

through the drive status window.

Deactivate the drive using the GUI control

panel maintenance menu.

Reseat drive.

Check cabling.

Load/unload a cartridge to the drive to

verify.

Check the tape cartridge used in the last

operation for damage.

Run the cartridge cycle diagnostic to

verify.

3082

Drive Stow Failed, Media Returned to

Source

Press the Enter button to clear the

message.

Use only media approved for the drive

type.

Invalid user initiated operation. Set

parameters correctly and try again.

3083

Drive Stow Failed, Media Remains in

Drive

Press the Enter button to clear the

message.

Invalid user initiated operation. Set

parameters correctly and try again.

Ensure cartridges are in magazines.

Table 10

Fault Symptom Codes (continued)

FSC

Message

ERP