Hitachi SJ700-2 Series User Manual

Page 11

Advertising
background image

1 - 7

Default

Code

Function name

Monitored data or setting

_FF _FEF _FUF

Note

b001

Selection of restart mode

00 (tripping), 01 (starting with 0 Hz), 02 (starting with matching frequency), 03
(tripping after deceleration and stopping with matching frequency), 04
(restarting with active matching frequency)

00

b002

Allowable under-voltage power
failure time

0.3 to 25.0 (s)

1.0

b003

Retry wait time before motor restart 0.3 to 100.0 (s)

1.0

b004

Instantaneous power
failure/under-voltage trip alarm
enable

00 (disabling), 01 (enabling), 02 (disabling during stopping and decelerating
to stop)

00

b005

Number of restarts on power
failure/under-voltage trip events

00 (16 times), 01 (unlimited)

00

b006

Phase loss detection enable

00 (disabling), 01 (enabling)

00

b007

Restart frequency threshold

0.00 to 99.99, 100.0 to 400.0 (Hz)

0.00

b008

Selection of retry after tripping

00 (tripping), 01 (starting with 0 Hz), 02 (starting with matching frequency), 03
(tripping after deceleration and stopping with matching frequency), 04
(restarting with active matching frequency)

00

b009

Selection of retry after undervoltage 00 (16 times), 01 (unlimited)

00

b010

Selection of retry count after
overvoltage or overcurrent

1 to 3 (times)

3

Restar

t a

fte

r insta

ntaneo

us power

f

ailur

e o

r tr

ipping

b011

Retry wait time after tripping

0.3 to 100.0 (s)

1.0

b012

Electronic thermal setting
(calculated within the inverter from
current output)

0.20 x "rated current" to 1.00 x "rated current" (A)

Rated current of inverter

b212

Electronic thermal setting
(calculated within the inverter from
current output), 2nd motor

0.20 x "rated current" to 1.00 x "rated current" (A)

Rated current of inverter

b312

Electronic thermal setting
(calculated within the inverter from
current output), 3rd motor

0.20 x "rated current" to 1.00 x "rated current" (A)

Rated current of inverter

b013 Electronic

thermal

characteristic

00 (reduced-torque characteristic), 01 (constant-torque characteristic), 02
(free setting)

00 01 01

b213

Electronic thermal characteristic, 2nd
motor

00 (reduced-torque characteristic), 01 (constant-torque characteristic), 02
(free setting)

00 01 01

b313

Electronic thermal characteristic, 3rd
motor

00 (reduced-torque characteristic), 01 (constant-torque characteristic), 02
(free setting)

00 01 01

b015

Free setting, electronic thermal
frequency (1)

0. to 400. (Hz)

0.

b016

Free setting, electronic thermal
current (1)

0.0 to rated current (A)

0.0

b017

Free setting, electronic thermal
frequency (2)

0. to 400. (Hz)

0.

b018

Free setting, electronic thermal
current (2)

0.0 to rated current (A)

0.0

b019

Free setting, electronic thermal
frequency (3)

0. to 400. (Hz)

0.

Elect

ronic t

her

m

al

funct

ion

b020

Free setting, electronic thermal
current (3)

0.0 to rated current (A)

0.0

b021

Overload restriction operation mode

00 (disabling), 01 (enabling during acceleration and deceleration), 02
(enabling during constant speed), 03 (enabling during acceleration and
deceleration (increasing the speed during regeneration))

01

b022

Overload restriction setting

0.20 x "rated current" to 1.00 x "rated current" (A)

Rated current of inverter x

1.50

b023

Deceleration rate at overload
restriction

0.10 to 30.00 (s)

1.00

b024

Overload restriction operation mode
(2)

00 (disabling), 01 (enabling during acceleration and deceleration), 02
(enabling during constant speed), 03 (enabling during acceleration and
deceleration (increasing the speed during regeneration))

01

b025

Overload restriction setting (2)

0.20 x "rated current" to 2.00 x "rated current" (A)

Rated current of inverter x

1.50

b026

Deceleration rate at overload restriction
(2)

0.10 to 30.00 (s)

1.00

b027

Overcurrent suppression enable

00 (disabling), 01 (enabling)

01

b028

Active frequency matching, scan
start frequency

0.20 x "rated current" to 2.00 x "rated current" (A)

Rated current of inverter

b029

Active frequency matching,
scan-time constant

0.10 to 30.00 (s)

0.50

O

ver

load

r

es

tr

ic

tion and

over

cur

rent r

estr

aint

b030

Active frequency matching, restart
frequency select

00 (frequency at the last shutoff), 01 (maximum frequency), 02 (set
frequency)

00

Soft

wa

re

lock

b031

Software lock mode selection

00 (disabling change of data other than "b031" when SFT is on), 01 (disabling
change of data other than "b031" and frequency settings when SFT is on), 02
(disabling change of data other than "b031"), 03 (disabling change of data
other than "b031" and frequency settings), 10 (enabling data changes during
operation)

01