Default

Code

Function name

Monitored data or setting

_FF _FEF

_FUF

Note

H001 Auto-tuning

Setting

00 (disabling auto-tuning), 01 (auto-tuning without rotation), 02 (auto-tuning
with rotation)

00

H002

Motor data selection, 1st motor

00 (Hitachi standard data), 01 (auto-tuned data),
02 (auto-tuned data [with online auto-tuning function])

00

H202

Motor data selection, 2nd motor

00 (Hitachi standard data), 01 (auto-tuned data),
02 (auto-tuned data [with online auto-tuning function])

00

H003

Motor capacity, 1st motor

0.20 to 75.00 (kW)

Factory setting

H203

Motor capacity, 2nd motor

0.20 to 75.00 (kW)

Factory setting

H004

Motor poles setting, 1st motor

2, 4, 6, 8, 10 (poles)

4

H204

Motor poles setting, 2nd motor

2, 4, 6, 8, 10 (poles)

4

H005

Motor speed constant, 1st motor

0.001 to 9.999, 10.00 to 80.00 (10.000 to 80.000)

1.590

H205

Motor speed constant, 2nd motor

0.001 to 9.999, 10.00 to 80.00 (10.000 to 80.000)

1.590

H006

Motor stabilization constant, 1st
motor

0. to 255.

100.

H206

Motor stabilization constant, 2nd
motor

0. to 255.

100.

H306

Motor stabilization constant, 3rd
motor

0. to 255.

100.

H020

Motor constant R1, 1st motor

0.001 to 9.999, 10.00 to 65.53 (

Ω)

Depending on motor capacity

H220

Motor constant R1, 2nd motor

0.001 to 9.999, 10.00 to 65.53 (

Ω)

Depending on motor capacity

H221

Motor constant R2, 1st motor

0.001 to 9.999, 10.00 to 65.53 (

Ω)

Depending on motor capacity

H221

Motor constant R2, 2nd motor

0.001 to 9.999, 10.00 to 65.53 (

Ω)

Depending on motor capacity

H222

Motor constant L, 1st motor

0.01 to 99.99, 100.0 to 655.3 (mH)

Depending on motor capacity

H222

Motor constant L, 2nd motor

0.01 to 99.99, 100.0 to 655.3 (mH)

Depending on motor capacity

H223

Motor constant Io

0.01 to 99.99, 100.0 to 655.3 (A)

Depending on motor capacity

H223

Motor constant Io, 2nd motor

0.01 to 99.99, 100.0 to 655.3 (A)

Depending on motor capacity

H224

Motor constant J

0.001 to 9.999, 10.00 to 99.99, 100.0 to 999.9, 1000. to 9999.

Depending on motor capacity

H224

Motor constant J, 2nd motor

0.001 to 9.999, 10.00 to 99.99, 100.0 to 999.9, 1000. to 9999.

Depending on motor capacity

H030

Auto constant R1, 1st motor

0.001 to 9.999, 10.00 to 65.53 (

Ω)

Depending on motor capacity

H230

Auto constant R1, 2nd motor

0.001 to 9.999, 10.00 to 65.53 (

Ω)

Depending on motor capacity

H231

Auto constant R2, 1st motor

0.001 to 9.999, 10.00 to 65.53 (

Ω)

Depending on motor capacity

H231

Auto constant R2, 2nd motor

0.001 to 9.999, 10.00 to 65.53 (

Ω)

Depending on motor capacity

H232

Auto constant L, 1st motor

0.01 to 99.99, 100.0 to 655.3 (mH)

Depending on motor capacity

H232

Auto constant L, 2nd motor

0.01 to 99.99, 100.0 to 655.3 (mH)

Depending on motor capacity

H233

Auto constant Io, 1st motor

0.01 to 99.99, 100.0 to 655.3 (A)

Depending on motor capacity

H233

Auto constant Io, 2nd motor

0.01 to 99.99, 100.0 to 655.3 (A)

Depending on motor capacity

H234

Auto constant J, 1st motor

0.001 to 9.999, 10.00 to 99.99, 100.0 to 999.9, 1000. to 9999.

Depending on motor capacity

Cont

ro

l cons

tan

ts

H234

Auto constant J, 2nd motor

0.001 to 9.999, 10.00 to 99.99, 100.0 to 999.9, 1000. to 9999.

Depending on motor capacity