2- 4

Name Description

Display on

digital operator

Display on remote

operator

Troubleshooting and corrective action

Option 2

error

The inverter detects errors in the option
board mounted in the optional slot 2.
For details, refer to the instruction
manual for the mounted option board.

Check whether the option board is
mounted correctly.

(Check the board mounting.)

Check whether the option board is used
correctly.

(Check the instruction manual for the

option board.)

Waiting in

undervoltage

status

If the input voltage falls, the inverter will
shut off its output, display the code
shown on the right, and wait for the
recovery of the input voltage.
The inverter will display the same error
code also during an instantaneous
power failure.
(remark) Inverter trips with under
voltage when this status continues for
40 seconds.

Check whether the power supply voltage
has fallen.

(Recover the power supply.)

Check the MCB and magnetic contactors
for poor contacts.

(Replace the MCB and magnetic

contactors.)

Check whether the voltage across the P
and N terminals is normal.

(Check the voltage across the P and N

terminals.)

Communica-

tion error

If a problem occurs in the
communication between the digital
operator and inverter, the inverter will
display the code shown on the right.

Check whether the relay plug is fitted
correctly.

(Check the relay plug for connection.)

Check whether the digital operator is
connected correctly.
(Check the digital operator for connection.)

Waiting for

retry

When the retry after instantaneous
power failure or tripping has been
enabled, the inverter displays the code
shown on the right while awaiting retry
after an instantaneous power failure or
tripping.

Power-off

The inverter displays the code shown
on the right when the inverter power is
turned off.

Restricted

operation

command

When an operation direction has been
restricted by the setting of "b035", the
inverter will display the error code
shown on the right if the operation
command specifying the restricted
operation direction is input.

Empty trip

history

If the inverter has not tripped before,the
inverter displays .



to

OP2-0

OP2-9

UV.WAIT

R-ERROR COMM<1>

RESTART

ADJUST

POWER OFF

RUN.CMD DISABLE

R-ERROR COMM<2>