Hitachi SJ700-2 Series User Manual

Page 16

Advertising
background image

1 - 12

Default

Code

Function name

Monitored data or setting

_FF _FEF _FUF

Note

C038

Low-current indication signal
output mode selection

00 (output during acceleration/deceleration and constant-speed operation),
01 (output only during constant-speed operation)

01

C039

Low-current indication signal
detection level

0.0 to 2.00 x "rated current" (A)

Rated current of

inverter

C040

Overload signal output mode

00 (output during acceleration/deceleration and constant-speed operation),
01 (output only during constant-speed operation)

01

C041

Overload level setting

0.0 to 2.00 x "rated current" (A)

Rated current of

inverter

C042

Frequency arrival setting for accel. 0.00 to 99.99, 100.0 to 400.0 (Hz)

0.00

C043

Frequency arrival setting for decel. 0.00 to 99.99, 100.0 to 400.0 (Hz)

0.00

C044

PID deviation level setting

0.0 to 100.0 (%)

3.0

C045

Frequency arrival setting for
acceleration (2)

0.00 to 99.99, 100.0 to 400.0 (Hz)

0.00

C046

Frequency arrival setting for
deceleration (2)

0.00 to 99.99, 100.0 to 400.0 (Hz)

0.00

C052

Maximum PID feedback data

0.0 to 100.0 (%)

100.0

C053

Minimum PID feedback data

0.0 to 100.0 (%)

0.0

C055

Over-torque (forward-driving) level
setting

0. to 200. (%)

100.

C056

Over-torque (reverse
regenerating) level setting

0. to 200. (%)

100.

C057

Over-torque (reverse driving) level
setting

0. to 200. (%)

100.

C058

Over-torque (forward
regenerating) level setting

0. to 200. (%)

100.

C061

Electronic thermal warning level
setting

0. to 100. (%)

80.

C062

Alarm code output

00 (disabling), 01 (3 bits), 02 (4 bits)

00

C063

Zero speed detection level

0.00 to 99.99, 100.0 (Hz)

0.00

Levels and ou

tput t

er

m

inal sta

tus

C064

Heat sink overheat warning level

0. to 200.0 (

°C)

120.

C071

Communication speed selection

02 (loopback test), 03 (2,400 bps), 04 (4,800 bps), 05 (9,600 bps), 06
(19,200 bps)

04

C072

Node allocation

1. to 32.

1.

C073

Communication data length
selection

7 (7 bits), 8 (8 bits)

7

C074

Communication parity selection

00 (no parity), 01 (even parity), 02 (odd parity)

00

C075

Communication stop bit selection

1 (1 bit), 2 (2 bits)

1

C076

Selection of the operation after
communication error

00 (tripping), 01 (tripping after decelerating and stopping the motor), 02
(ignoring errors), 03 (stopping the motor after free-running), 04
(decelerating and stopping the motor)

02

C077

Communication timeout limit
before tripping

0.00 to 99.99 (s)

0.00

C078

Communication wait time

0. to 1000. (ms)

0.

Com

m

unica

tion f

unc

tion

C079

Communication mode selection

00(ASCII), 01(Modbus-RTU)

00

C081

[O] input span calibration

0. to 9999., 1000 to 6553(10000 to 65530)

Factory setting

C082

[OI] input span calibration

0. to 9999., 1000 to 6553(10000 to 65530)

Factory setting

C083

[O2] input span calibration

0. to 9999., 1000 to 6553(10000 to 65530)

Factory setting

C085

Thermistor input tuning

0.0 to 999.9, 1000.

Factory setting

Adjust

m

ent

C091

Debug mode enable

(Do not change this parameter, which is intended for factory adjustment.)

00

C101

Up/Down memory mode selection 00 (not storing the frequency data), 01 (storing the frequency data)

00

C102 Reset

mode

selection

00 (resetting the trip when RS is on), 01 (resetting the trip when RS is off), 2
(enabling resetting only upon tripping [resetting when RS is on])

00

Oth

er

s

C103

Restart mode after reset

00 (starting with 0 Hz), 01 (starting with matching frequency), 02 (restarting
with active matching frequency),03(resetting only trip)

00

C105

FM gain adjustment

50. to 200. (%)

100.

C106

AM gain adjustment

50. to 200. (%)

100.

C107

AMI gain adjustment

50. to 200. (%)

100.

C109

AM bias adjustment

0. to 100. (%)

0.

Me

te

r

adjust

m

en

t

C110

AMI bias adjustment

0. to 100. (%)

20.