Hitachi SJ700-2 Series User Manual
Page 15
![background image](/manuals/98550/15/background.png)
1 - 11
Default
Code
Function name
Monitored data or setting
_FF _FEF
_FUF
Note
C021
Terminal [11] function
01
C022
Terminal [12] function
00
C023
Terminal [13] function
03
C024
Terminal [14] function
07
C025
Terminal [15] function
40
In
te
lligent
ou
tput t
er
m
inals
C026
Alarm relay terminal function
00 (RUN: running), 01 (FA1: constant-speed reached), 02 (FA2: set
frequency overreached), 03 (OL: overload notice advance signal (1)), 04
(OD: output deviation for PID control), 05 (AL: alarm signal), 06 (FA3: set
frequency reached), 07 (OTQ: over-torque), 08 (IP: instantaneous power
failure), 09 (UV: undervoltage), 10 (TRQ: torque limited), 11 (RNT:
operation time over), 12 (ONT: plug-in time over), 13 (THM: thermal alarm
signal), 19 (BRK: brake release), 20 (BER: braking error), 21 (ZS: 0 Hz
detection signal), 22 (DSE: speed deviation maximum), 23 (POK:
positioning completed), 24 (FA4: set frequency overreached 2), 25 (FA5:
set frequency reached 2), 26 (OL2: overload notice advance signal (2)), 27
(Odc: Analog O disconnection detection), 28 (OIDc: Analog OI
disconnection detection), 29 (O2Dc: Analog O2 disconnection detection),
31 (FBV: PID feedback comparison), 32 (NDc: communication line
disconnection), 33 (LOG1: logical operation result 1), 34 (LOG2: logical
operation result 2), 35 (LOG3: logical operation result 3), 36 (LOG4: logical
operation result 4), 37 (LOG5: logical operation result 5), 38 (LOG6: logical
operation result 6), 39 (WAC: capacitor life warning), 40 (WAF: cooling-fan
speed drop), 41 (FR: starting contact signal), 42 (OHF: heat sink overheat
warning), 43 (LOC: low-current indication signal), 44 (M01:
general-purpose output 1), 45 (M02: general-purpose output 2), 46 (M03:
general-purpose output 3), 47 (M04: general-purpose output 4), 48 (M05:
general-purpose output 5), 49 (M06: general-purpose output 6), 50 (IRDY:
inverter ready), 51 (FWR: forward rotation), 52 (RVR: reverse rotation), 53
(MJA: major failure), 54(WCO: window comparator O), 55(WCOI: window
comparator OI), 56 (WCO2: window comparator O2)
(When alarm code output is selected for "C062", functions "AC0" to "AC2"
or "AC0" to "AC3" [ACn: alarm code output] are forcibly assigned to
intelligent output terminals 11 to 13 or 11 to 14, respectively.)
05
C027
[FM] siginal selection
00 (output frequency), 01 (output current), 02 (output torque), 03 (digital
output frequency), 04 (output voltage), 05 (input power), 06 (electronic
thermal overload), 07 (LAD frequency), 08 (digital current monitoring), 09
(motor temperature), 10 (heat sink temperature), 12 (general-purpose
output YA0)
00
C028
[AM] siginal selection
00 (output frequency), 01 (output current), 02 (output torque), 04 (output
voltage), 05 (input power), 06 (electronic thermal overload), 07 (LAD
frequency), 09 (motor temperature), 10 (heat sink temperature), 11 (output
torque [signed value]), 13 (general-purpose output YA1)
00
C029
[AMI] siginal selection
00 (output frequency), 01 (output current), 02 (output torque), 04 (output
voltage), 05 (input power), 06 (electronic thermal overload), 07 (LAD
frequency), 09 (motor temperature), 10 (heat sink temperature), 14
(general-purpose output YA2)
00
Analog m
onit
or
ing
C030
Digital current monitor reference
value
0.20 x "rated current" to 2.00 x "rated current" (A)
(Current with digital current monitor output at 1,440 Hz)
Rated current of
inverter
C031
Terminal [11] active state
00 (NO) / 01 (NC)
00
C032
Terminal [12] active state
00 (NO) / 01 (NC)
00
C033
Terminal [13] active state
00 (NO) / 01 (NC)
00
C034
Terminal [14] active state
00 (NO) / 01 (NC)
00
C035
Terminal [15] active state
00 (NO) / 01 (NC)
00
In
te
lligent
ou
tput
te
rm
inals
C036
Alarm relay active state
00 (NO) / 01 (NC)
01