3 extended function mode – Hitachi SJ700-2 Series User Manual

Page 8

Advertising
background image

1 - 4

1.2.3 Extended Function Mode

Default

Code

Function name

Monitored data or setting

_FF _FEF

_FUF

Note

A001

Frequency source setting

00 (keypad potentiometer) (*1), 01 (control circuit terminal block), 02 (digital
operator), 03 (RS485), 04 (option 1), 05 (option 2), 06 (pulse-string input), 07
(easy sequence), 10 (operation function result)

02 01 01

A002

Run command source setting

01 (control circuit terminal block), 02 (digital operator), 03 (RS485), 04 (option
1), 05 (option 2)

02 01 01

A003

Base frequency setting

30. to "maximum frequency " (Hz)

60.

50.

60.

A203

Base frequency setting, 2nd
motor

30. to "maximum frequency, 2nd motor" (Hz)

60. 50. 60.

A303

Base frequency setting, 3rd
motor

30. to "maximum frequency, 3rd motor" (Hz)

60. 50. 60.

A004

Maximum frequency setting

30. to 400. (Hz)

60.

50.

60.

A204

Maximum frequency setting, 2nd
motor

30. to 400. (Hz)

60. 50. 60.

Basic set

tings

A304

Maximum frequency setting, 3rd
motor

30. to 400. (Hz)

60. 50. 60.

A005

[AT] selection

00 (switching between O and OI terminals), 01 (switching between O and O2
terminals), 02 (switching between O terminal and keypad potentiometer) (*1),
03 (switching between OI terminal and keypad potentiometer) (*1), 04
(switching between O2 and keypad potentiometer) (*1)

00

A006

[O2] selection

00 (single), 01 (auxiliary frequency input via O and OI terminals)
(nonreversible), 02 (auxiliary frequency input via O and OI terminals)
(reversible), 03 (disabling O2 terminal)

03

A011

[O]-[L] input active range start
frequency

0.00 to 99.99, 100.0 to 400.0 (Hz)

0.00

A012

[O]-[L] input active range end
frequency

0.00 to 99.99, 100.0 to 400.0 (Hz)

0.00

A013

[O]-[L] input active range start
voltage

0. to "[O]-[L] input active range end voltage" (%)

0.

A014

[O]-[L] input active range end
voltage

"[O]-[L] input active range start voltage" to 100. (%)

100.

A015

[O]-[L] input active range start
frequency selection

00 (external start frequency), 01 (0 Hz)

01

A016

External frequency filter time
const.

1. to 30. or 31. (500 ms filter ±0.1 Hz with hysteresis)

31.

Analog input

and o

the

rs

A017

Easy sequence function
selection

00 (disabling), 01 (enabling)

00

A019

Multispeed operation selection

00 (binary: 16 speeds selectable with 4 terminals), 01 (bit: 8 speeds selectable
with 7 terminals)

00

A020

Multispeed frequency setting

0.0 or “start frequency” to “maximum frequency” (Hz)

0.00

A220

Multispeed frequency setting,
2nd motor

0.0 or “start frequency” to “maximum frequency, 2nd motor” (Hz)

0.00

A320

Multispeed frequency setting,
3rd motor

0.0 or “start frequency” to “maximum frequency, 3rd motor” (Hz)

0.00

A021

Multispeed 1 setting

0.0 or “start frequency” to “1st maximum frequency” (Hz)

0.00

A022

Multispeed 2 setting

0.0 or “start frequency” to “2nd maximum frequency” (Hz)

0.00

A023

Multispeed 3 setting

0.0 or “start frequency” to “3rd maximum frequency” (Hz)

0.00

A024

Multispeed 4 setting

0.0 or “start frequency” to “n-th maximum frequency” (Hz)

0.00

A025

Multispeed 5 setting

0.0 or “start frequency” to “n-th maximum frequency” (Hz)

0.00

A026

Multispeed 6 setting

0.0 or “start frequency” to “n-th maximum frequency” (Hz)

0.00

A027

Multispeed 7 setting

0.0 or “start frequency” to “n-th maximum frequency” (Hz)

0.00

A028

Multispeed 8 setting

0.0 or “start frequency” to “n-th maximum frequency” (Hz)

0.00

A029

Multispeed 9 setting

0.0 or “start frequency” to “n-th maximum frequency” (Hz)

0.00

A030

Multispeed 10 setting

0.0 or “start frequency” to “n-th maximum frequency” (Hz)

0.00

A031

Multispeed 11 setting

0.0 or “start frequency” to “n-th maximum frequency” (Hz)

0.00

A032

Multispeed 12 setting

0.0 or “start frequency” to “n-th maximum frequency” (Hz)

0.00

A033

Multispeed 13 setting

0.0 or “start frequency” to “n-th maximum frequency” (Hz)

0.00

A034

Multispeed 14 setting

0.0 or “start frequency” to “n-th maximum frequency” (Hz)

0.00

A035

Multispeed 15 setting

0.0 or “start frequency” to “n-th maximum frequency” (Hz)

0.00

A038

Jog frequency setting

"Start frequency" to 9.99 (Hz)

1.00

M

ult

ispeed ope

ra

tion

an

d jogging

A039 Jog

stop

mode

00 (free-running after jogging stops [disabled during operation]), 01
(deceleration and stop after jogging stops [disabled during operation]), 02 (DC
braking after jogging stops [disabled during operation]), 03 (free-running after
jogging stops [enabled during operation]), 04 (deceleration and stop after
jogging stops [enabled during operation]), 05 (DC braking after jogging stops
[enabled during operation])

00

.

Advertising