1 - 9

Default

Code

Function name

Monitored data or setting

_FF

_FEF _FUF

Note

b078

Cumulative input power data
clearance

Clearance by setting "01" and pressing the STR key

00

b079

Cumulative input power display
gain setting

1. to 1000.

1.

b082

Start frequency adjustment

0.10 to 9.99 (Hz)

0.50

b083

Carrier frequency setting

0.5 to 15.0 (kHz) (subject to derating)

5.0

b084

Initialization mode (parameters or
trip history)

00 (clearing the trip history), 01 (initializing the data),
02 (clearing the trip history and initializing the data)

00

b085

Country code for initialization

00 (Japan), 01 (EU), 02 (U.S.A.)

00

01

02

b086

Frequency scaling conversion
factor

0.1 to 99.0

1.0

b087

STOP key enable

00 (enabling), 01 (disabling), 02 (disabling only the function to stop)

00

b088

Restart mode after FRS

00 (starting with 0 Hz), 01 (starting with matching frequency), 02 (starting
with active matching frequency)

00

b089

Automatic carrier frequency
reduction

00: invalid, 01: valid

00

b090

Dynamic braking usage ratio

0.0 to 100.0 (%)

0.0

b091

Stop mode selection

00 (deceleration until stop), 01 (free-run stop)

00

b092 Cooling

fan

control

00 (always operating the fan), 01 (operating the fan only during inverter
operation [including 5 minutes after power-on and power-off])

00

b095

Dynamic braking control

00 (disabling), 01 (enabling [disabling while the motor is topped]), 02
(enabling [enabling also while the motor is topped])

00

b096

Dynamic braking activation level

330 to 380, 660 to 760(V)

360/

720

b098

Thermistor for thermal protection
control

00 (disabling the thermistor), 01 (enabling the thermistor with PTC), 02
(enabling the thermistor with NTC)

00

Oth

er

s

b099

Thermal protection level setting

0. to 9999. (

Ω)

3000.

b100

Free-setting V/f frequency (1)

0. to "free-setting V/f frequency (2)" (Hz)

0.

b101

Free-setting V/f voltage (1)

0.0 to 800.0 (V)

0.0

b102

Free-setting V/f frequency (2)

0. to "free-setting V/f frequency (3)" (Hz)

0.

b103

Free-setting V/f voltage (2)

0.0 to 800.0 (V)

0.0

b104

Free-setting V/f frequency (3)

0. to "free-setting V/f frequency (4)" (Hz)

0.

b105

Free-setting V/f voltage (3)

0.0 to 800.0 (V)

0.0

b106

Free-setting V/f frequency (4)

0. to "free-setting V/f frequency (5)" (Hz)

0.

b107

Free-setting V/f voltage (4)

0.0 to 800.0 (V)

0.0

b108

Free-setting V/f frequency (5)

0. to "free-setting V/f frequency (6)" (Hz)

0.

b109

Free-setting V/f voltage (5)

0.0 to 800.0 (V)

0.0

b110

Free-setting V/f frequency (6)

0. to "free-setting V/f frequency (7)" (Hz)

0.

b111

Free-setting V/f voltage (6)

0.0 to 800.0 (V)

0.0

b112

Free-setting V/f frequency (7)

0. to 400. (Hz)

0.

F

re

e se

tti

ng

o

f V

/f ch

ar

ac

te

ris

tic

b113

Free-setting V/f voltage (7)

0.0 to 800.0 (V)

0.0

b120

Brake Control Enable

00 (disabling), 01 (enabling)

00

b121

Brake Wait Time for Release

0.00 to 5.00 (s)

0.00

b122

Brake Wait Time for Acceleration

0.00 to 5.00 (s)

0.00

b123

Brake Wait Time for Stopping

0.00 to 5.00 (s)

0.00

b124

Brake Wait Time for Confirmation

0.00 to 5.00 (s)

0.00

b125

Brake Release Frequency Setting 0.00 to 99.99, 100.0 to 400.0 (Hz)

0.00

b126

Brake Release Current Setting

0.0 to 2.00 x "rated current"

Rated current of inverter

b127

Braking frequency

0.00 to 99.99, 100.0 to 400.0 (Hz)

0.00

b130

Overvoltage suppression enable

00 (disabling the restraint), 01 (controlled deceleration), 02 (enabling
acceleration)

00

b131

Overvoltage suppression level

330 to 390 (V) (200 V class model), 660 to 780 (V) (400 V class model)

380/

760

b132

Acceleration and deceleration
rate at overvoltage suppression

0.10 to 30.00 (s)

1.00

b133

Overvoltage suppression
propotional gain

0.00 to 2.55

0.50

Oth

er

s

b134

Overvoltage suppression Integral
time

0.000 to 9.999 / 10.00 to 65.53 (s)

0.060