2 function mode – Hitachi SJ700-2 Series User Manual

Page 7

Advertising
background image

1 - 3

Code

Function name

Monitored data or setting

Default

Note

d025

User monitor 0

-2147483647 to 2147483647 (upper 4 digits including “-“)

d026

User monitor 1

-2147483647 to 2147483647 (upper 4 digits including “-“)

d027

User monitor 2

-2147483647 to 2147483647 (upper 4 digits including “-“)

d028

Pulse counter

0 to 2147483647 (upper 4 digits)

d029

Position setting monitor

-1073741823 to 1073741823 (upper 4 digits including “-“)

d030

Position feedback monitor

-1073741823 to 1073741823 (upper 4 digits including “-“)

d080

Trip Counter

0. to 9999., 1000 to 6553 (10000 to 65530) (times)

d081

Trip monitoring 1

Factor, frequency (Hz), current (A), voltage across P-N (V), running time (hours),
power-on time (hours)

d082

Trip monitoring 2

Factor, frequency (Hz), current (A), voltage across P-N (V), running time (hours),
power-on time (hours)

d083

Trip monitoring 3

Factor, frequency (Hz), current (A), voltage across P-N (V), running time (hours),
power-on time (hours)

d084

Trip monitoring 4

Factor, frequency (Hz), current (A), voltage across P-N (V), running time (hours),
power-on time (hours)

d085

Trip monitoring 5

Factor, frequency (Hz), current (A), voltage across P-N (V), running time (hours),
power-on time (hours)

d086

Trip monitoring 6

Factor, frequency (Hz), current (A), voltage across P-N (V), running time (hours),
power-on time (hours)

d090

Programming error monitoring

Warning code

d102

DC voltage monitoring

0.0 to 999.9 (V)

d103

BRD load factor monitoring

0.0 to 100.0 (%)

d104

Electronic thermal overload monitoring

0.0 to 100.0 (%)


1.2.2 Function Mode

Default

Code

Function name

Monitored data or setting

_FF

_FEF

_FUF

F001

Output frequency setting

0.0, "start frequency" to "maximum frequency" (or maximum frequency,
2nd/3rd motors) (Hz)
0.0 to 100.0 (when PID function is enabled)

0.00

F002

Acceleration (1) time setting

0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s)

30.00

F202

Acceleration (1) time setting, 2nd
motor

0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s)

30.00

F302

Acceleration (1) time setting, 3rd
motor

0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s)

30.00

F003

Deceleration (1) time setting

0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s)

30.00

F203

Deceleration time setting, 2nd motor 0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s)

30.00

F303

Deceleration time setting, 3rd motor

0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s)

30.00

F004

Keypad Run key routing

00 (forward rotation), 01 (reverse rotation)