1 - 8

Default

Code

Function name

Monitored data or setting

_FF _FEF

_FUF

Note

b034

Run/power-on warning time

0. to 9999. (0 to 99990), 1000 to 6553 (10000 to 655300) (hr)

0.

b035 Rotational

direction

restriction

00 (enabling both forward and reverse rotations), 01 (enabling only
forward rotation), 02 (enabling only reverse rotation)

00

b036

Reduced voltage start selection

0 (minimum reduced voltage start time) to 255 (maximum reduced voltage
start time)

6

b037

Function code display restriction

00 (full display), 01 (function-specific display), 02 (user setting), 03 (data
comparison display), 04 (basic display)

04

b038 Initial-screen

selection

00 (screen displayed when the STR key was pressed last), 01 (d001), 02
(d002), 03 (d003), 04 (d007), 05 (F001)

01

Oth

er

s

b039

Automatic user-parameter
setting function enable

00 (disabling), 01 (enabling)

00

b040

Torque limit selection

00 (quadrant-specific setting), 01 (switching by terminal), 02 (analog
input), 03 (option 1), 04 (option 2)

00

b041

Torque limit (1) (forward-driving
in 4-quadrant mode)

0. to 200. (%), no (disabling torque limitation)

150.

b042

Torque limit (2)
(reverse-regenerating in
4-quadrant mode)

0. to 200. (%), no (disabling torque limitation)

150.

b043

Torque limit (3) (reverse-driving
in 4-quadrant mode)

0. to 200. (%), no (disabling torque limitation)

150.

b044

Torque limit (4)
(forward-regenerating in
4-quadrant mode)

0. to 200. (%), no (disabling torque limitation)

150.

b045

Torque limit LADSTOP enable

00 (disabling), 01 (enabling)

00

To

rque lim

itat

ion

b046

Reverse Run protection enable

00 (disabling), 01 (enabling)

00

b050

Controller deceleration and stop
on power loss

00 (disabling), 01 (nonstop deceleration to stop), 02 (DC voltage constant
control, with resume), 03 ( without resume)

00

b051

DC bus voltage trigger level
during power loss

0.0 to 999.9, 1000. (V)

220/440

b052

Over-voltage threshold during
power loss

0.0 to 999.9, 1000. (V)

360/720

b053

Deceleration time setting during
power loss

0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s)

1.00

b054

Initial output frequency decrease
during power loss

0.00 to 10.00 (Hz)

0.00

b055

Proportional gain setting for
nonstop operation at power loss

0.00 to 2.55

0.20

Non-

st

op

oper

at

ion at

m

om

en

tar

y power

fa

ilur

e

b056

Integral time setting for nonstop
operation at power loss

0.000 to 9.999 /10.00 to 65.53 (s)

0.100

b060

Maximum-limit level of window
comparators O

0. to 100. (lower limit : b061 + b062 / 2) (%)

100

b061

Minimum-limit level of window
comparators O

0. to 100. (lower limit : b060 - b062 / 2) (%)

0

b062

Hysteresis width of window
comparators O

0. to 10. (lower limit : b061 - b062 / 2) (%)

0

b063

Maximum-limit level of window
comparators OI

0. to 100. (lower limit : b064 + b066 / 2) (%)

100

b064

Minimum-limit level of window
comparators OI

0. to 100. (lower limit : b063 - b066 / 2) (%)

0

b065

Hysteresis width of window
comparators OI

0. to 10. (lower limit : b063 - b064 / 2) (%)

0

b066

Maximum-limit level of window
comparators OI

-100. to 100. (lower limit : b067 + b068 / 2) (%)

100

b067

Minimum-limit level of window
comparators O/OI/O2

-100. to 100. (lower limit : b066 - b068 / 2) (%)

0

b068

Hysteresis width of window
comparators O/OI/O2

0. to 10. (lower limit : b066 - b067 / 2) (%)

0

b070

Operation level at O
disconnection

0. to 100. (%) or "no" (ignore)

no

b071

Operation level at OI
disconnection

0. to 100. (%) or "no" (ignore)

no

Window com

par

at

or

b072

Operation level at O2
disconnection

-100. to 100. (%) or "no" (ignore)

no