Hitachi SJ700-2 Series User Manual

Page 43

Advertising
background image

3.4 Inverter Setting

The logic board is common to all inverter models. If you change the inverter capacity or voltage class, you must
also adjust the relevant settings of the logic board to those of the inverter.

3.4.1 Setting procedure

(1) Prepare for power-on.

(1.1) Connect the digital operator to the inverter.

(2) Turn the inverter power on.

(2.1) Select "00" (ALL) for the display selection (b037).

(3) Set the region, output capacity, voltage class, and default data codes.
(3.1) Switch the inverter to debug mode.

(Setting method)

Display code "C091" on the monitor, press the FUNC key, enter "01", and then press the STR key.

(3.2)Set the region code.
(Setting method)
Display code "C195" on the monitor, press the FUNC key, select one of the codes listed in the table below, and

then press the STR key.

Region where to

use the inverter

Region code

(C195)

Japan

JP

Europe

EU

U.S.A.

USA

Note: Do not set any code other than "JP".

(3.3) Set the capacity code.

(Setting method)

Display code "C196" on the monitor, press the FUNC key, select one of the codes listed in the table below, and
then press the STR key.

Inverter model

Capacity code

(C196)

150LF**/150HF**

15.0

185LF**/185HF**

18.5

220LF**/220HF**

22.0

300LF**/300HF**

30.0

370LF**/370HF**

37.0


(3.4) Set the voltage class code.

(Setting method)

Display code "C196" on the monitor, press the FUNC key, select one of the codes listed in the table below, and
then press the STR key.

Voltage class

Voltage class

(C197)

200 V class

200

400 V class

400


(3.5) Select default data.

(Setting method)

Display code "b085" on the monitor, press the FUNC key, select one of the codes listed in the table below,

and then press the STR key.

Region where to

use the inverter

Default data code

(b085)

for Japan

00

for Europe

01

for the U.S.A.

02


(4) Perform data initialization. (See Section 2.5.)
(5) After initialization ends (with code "d001" displayed on the monitor), turn the inverter power off.
(6) Turn the inverter power on.

Advertising