3. SIGNALS AND WIRING

3.13.1 Connection example

Wire the power supply/main circuit as shown below so that power is shut off and the servo-on signal
turned off as soon as an alarm occurs, a servo emergency stop is made valid, a controller emergency stop,
or a servo motor thermal relay alarm is made valid. A no-fuse breaker (NFB) must be used with the input
cables of the power supply.

L

1

L

2

L

3

L

11

L

21

EMG

SON

SG

CN2

U

V

W

U

V

W

M

BU

RA2

BV

BW

MC

SK

ON

MC

NFB

MC

OHS2

OHS1

ALM

COM

VDD

RA1

Servo motor

thermal relay

RA2

Alarm

RA1

emergency stop

OFF

3-phase
200 to 230VAC

Servo amplifier

(Note 1)

Dynamic

break

Servo motor

HA-LFS series

Encoder

(Note 2)

Servo motor

thermal relay

24VDC
power supply

Emergency stop
servo-on

MR-JHSCBL M

cable

Trouble

P

P

1

(Note 3)

Cooling fan

Note 1. When using the external dynamic break, refer to section 13.1.4.

2. Cooling fan power supply of the HA-LFS11K2 servo motor is 1-phase. Power supply specification of the cooling fan is

different from that of the servo amplifier. Therefore, separate power supply is required.

3. Always connect P

1

and P. (Factory-wired). When using the power factor improving DC reactor, refer to section 13.2.4.