4 torque control mode, Operation – MITSUBISHI ELECTRIC MR-J2S- A User Manual

Page 122

Advertising
background image

4 - 5

4. OPERATION

(6) Stop

In any of the following statuses, the servo amplifier interrupts and stops the operation of the servo

motor.

Refer to section 3.9 (2) for the servo motor equipped with electromagnetic brake. Note that

simultaneous ON or simultaneous OFF of stroke end (LSP, LSN) OFF and forward rotation start

(ST1) or reverse rotation start (ST2) has the same stop pattern as described below.

(a) Servo-on (SON) OFF

The base circuit is shut off and the servo motor coasts.

(b) Alarm occurrence

When an alarm occurs, the base circuit is shut off and the dynamic brake is operated to bring the

servo motor to a sudden stop.

(c) Emergency stop (EMG) OFF

The base circuit is shut off and the dynamic brake is operated to bring the servo motor to a sudden

stop. Alarm AL.E6 occurs.

(d) Stroke end (LSP/LSN) OFF

The servo motor is brought to a sudden stop and servo-locked. The motor may be run in the

opposite direction.

(e) Simultaneous ON or simultaneous OFF of forward rotation start (ST1) and reverse rotation start

(ST2)

The servo motor is decelerated to a stop.

POINT

A sudden stop indicates deceleration to a stop at the deceleration time
constant of zero.

4.2.4 Torque control mode

(1) Power on

1) Switch off the servo-on (SON).
2) When main circuit power/control circuit power is switched on, the display shows "U (torque

command voltage)", and in two second later, shows data.

(2) Test operation

Using jog operation in the test operation mode, operate at the lowest speed to confirm that the servo
motor operates. (Refer to section 6.8.2.)

(3) Parameter setting

Set the parameters according to the structure and specifications of the machine. Refer to chapter 5 for

the parameter definitions and to sections 6.5 for the setting method.

Description

Parameter No.

Name

Setting

Control mode, regenerative option
selection

Position control mode
MR-RB12 regenerative option is used.

0

8

1000

9

1500

2

0

2

1

Input filter 3.555ms(initial value)
Electromagnetic brake interlock (MBR) is not used.

Set 1000r/min.
Set 1500r/min.

1

Internal speed command 2

Internal speed command 1

Function selection 1

10

Internal speed command 3

11

Acceleration time constant

12

Deceleration time constant

13

S-pattern acceleration/deceleration
time constant

2000
1000

500

0

Set 2000r/min.
Set 1000ms.
Set 500ms.

Not used

14

Torque command time constant

28

Internal torque limit 1

2000

50

Set 2000ms.
Controlled to 50 output.

After setting the above parameters, switch power off once. Then switch power on again to make the set

parameter values valid.