3. SIGNALS AND WIRING

3.7.2 Terminals

The positions and signal arrangements of the terminal blocks change with the capacity of the servo
amplifier. Refer to section 11.1.

Symbol

Connection Target

(Application)

Description

Supply L

1

, L

2

and L

3

with the following power.

For 1-phase 230VAC, connect the power supply to L

1

,

L

2

and leave L

3

open.

Servo amplifier

Power supply

MR-J2S-10A to

70A

MR-J2S-100A

to 22kA

MR-J2S-10A1

to 40A1

3-phase 200 to 230VAC,
50/60Hz

L

1

L

2

L

3

1-phase 230VAC,
50/60Hz

L

1

L

2

1-phase 100 to 120VAC,
50/60Hz

L

1

L

2

L

1

, L

2

, L

3

Main circuit power supply

U, V, W

Servo motor output

Connect to the servo motor power supply terminals (U, V, W).
During power-on, do not open or close the motor power line. Otherwise, a
malfunction or faulty may occur.
Supply L

11

and L

12

with the following power.

Servo amplifier

Power supply

MR-J2S-10A to 700A

MR-J2S-10A1 to 40A1

1-phase 200 to 230VAC,
50/60Hz

L

11

L

21

1-phase 100 to 120VAC,
50/60Hz

L

11

L

21

L

11

, L

21

Control circuit power supply

P

1

Power factor improving DC

reactor

When not using the power factor improving DC reactor, connect P

1

and P.

(Factory-wired.)
When using the power factor improving DC reactor, disconnect the wiring across
P

1

-P

2

and connect the power factor improving DC reactor across P

1

-P.

The power factor improving DC reactor can be used with MR-J2S-11KA to 22KA.
(Refer to section 13.2.4.)

P, C, D

Regenerative option

1) MR-J2S-350A or less

When using servo amplifier built-in regenerative resistor, connect P and D.
(Wired by default)
When using regenerative option, disconnect between P-D terminals and
connect regenerative option to P terminal and C terminal.

2) MR-J2S-500A 700A

MR-J2S-500A 700A do not have D terminal.
When using servo amplifier built-in regenerative resistor, connect P terminal
and C terminal. (Wired by default)
When using regenerative option, disconnect P terminal and C terminal and
connect regenerative option to P terminal and C terminal.

3) MR-J2S-11KA to 22KA

MR-J2S-11KA to 22KA do not have D terminal.
When not using the power supply return converter and the brake unit, make
sure to connect the regenerative option to P terminal and C terminal.

Refer to section 13.1.1.

N

Return converter

Brake unit

When using the return converter or brake unit, connect it across P-N.
Do not connect it to the servo amplifier of MR-J2S-200A or less.
Refer to sections 13.1.2 and 13.1.3 for details.

Protective earth (PE)

Connect this terminal to the protective earth (PE) terminals of the servo motor
and control box for grounding.