Measurement Specialties 9116 User Manual

Page 63

Advertising
background image

Pressure Systems, Inc. Model 9116 User’s Manual

Page 54

www.PressureSystems.com

Command ‘c’— Sub-command Index 02: Stop Stream(s)

This sub-command is used to stop (or temporarily suspend) the delivery of any previously
started host stream in a module, one at a time or all together, whether the stream was
“continuous” or “limited.” The sub-command’s format is:


Command

c 02 st

‘c’ is the command letter
‘02’ is the sub-command index (‘ii’) for Stop Stream
st’ is the stream id digit (single stream 1, 2, or 3, or 0=all streams)

NOTE: all parameters are separated by a space.


Response

A
‘A’ is the acknowledge letter


Autonomous
Packet

command stops generation of autonomous packets from the requested
stream(s).



Description: This sub-command stops the current “run” of a particular specified host stream

(st=1-3), or stops the current “run” of “all configured” host streams with a single

command

(st=0).

Any stopped stream may be resumed (i.e., restarted) with the Start Stream sub-
command as long as that stream remains defined in the module and any limited
sequence count has not yet expired. The Clear Stream sub-command may be
used to undefine a stream. Any continuous stream or unexpired limited stream
that is restarted continues generating new sequence numbers (i.e., at the count
where it left off when stopped). However, the stream must be reconfigured with
the Configure a Host Delivery Stream sub-command (00) before it restarts with
sequence count =1. Any expired limited stream must be reconfigured to restart
at all.

Example:

Stop all the streams configured in the previous example:

c 02 0


Read

response:


“A”

Advertising