101

Figure 75

Voltage Checks for Ignition Module and

Combination Gas Valve

Ignition Module

Voltage

Test Points Marked

Fused

Nonfused

MV/PV to PV

3 VAC

24 VAC

MV/PV to MV

12 VAC

24 VAC

Combination Gas Valve

TR to TH

12 VAC

24 VAC

TH/TR to TR

3 VAC

24 VAC

NOTE: Information on the fused ignition module is provided

for reference only. All ovens produced 1988 or later use the

nonfused module. The fused module is no longer available.

5. Burner Operation

a. Shut off the manual gas valve for oven. Turn the

Burner and Heat switches ON. The spark should

begin at the pilot burner within 30 seconds.
With the manual gas valve turned off, no gas will be

present; so, the spark will continue for the lockout

timing period of 90 seconds.

b. Turn the Heat switch OFF, then turn on the gas

supply. Set the temperature controller set point

above the actual oven temperature.

c. Turn the Heat switch ON. The system should start

as follows:
•

Spark turns on and pilot gas valve opens at

once. Pilot burner ignites after gas reaches

the pilot burner.

•

Spark cuts off when pilot flame is established.

•

Main gas valve opens and main burner lights

after gas reaches the burner ports.

NOTE: Main burner flame may not be satisfactory until

the gas input and combustion air have been adjusted.

6. Check Grounding

Electrical ground connections must be clean and tight.

If the lead wire is damaged or deteriorated, use only

No. 14 to 18 gauge, moisture-resistant thermoplastic

insulated wire with a 221°F (105°C) minimum rating as

a replacement.
Excessive temperature at the ceramic flame rod insu-

lator can also permit electrical leakage to ground.

Examine the flame rod and mounting bracket, and cor-

rect if it is bent out of position. Replace the ignitor/

sensor if the insulator is cracked.

7. Ignition Module Flame Sensor Circuit Test

The ignition module provides AC power to the ignitor/

sensor which the pilot burner flame rectifies to direct

current (DC). If the flame signal back to the control

module is not at least 2.0 mA DC, the system will lock

out.
The output of the flame sensing circuit cannot be

checked directly, so check the flame sensing circuit

indirectly by checking the flame sensing current form

the ignitor/sensor to the control module as follows.
a. Connect a ampmeter or multimeter set to read DC

microamps (mA) in series with the flame signal

ground wire. Disconnect the ground wire at the

control module. Connect the red (positive) lead of

the meter to the free end of the ground wire. Con-

nect the black (negative) meter lead to the ground

terminal on the ignition module.

b. Restart the system and read the meter. The flame

sensor current must be at least 2.0 mA, and the

reading must be steady. If the reading is below 2.0

mA or if the reading is unsteady, check the pilot

flame and electrical connections as described

above. Also, replace the ignitor/sensor if the ce-

ramic insulator is cracked.
If the reading still is unsteady, it may be necessary

to adjust the pilot pressure. Refer to Pilot Pres-

sure under Servicing the Combination Valve on Page

98.

8. System Troubleshooting.

Start the system by setting the temperature controller

above room temperature, and observe the system re-

sponse.
Establish the type of system malfunction or deviation

from normal operation by using the Intermittent Pilot

System Troubleshooting Table on Page 103.
Use the table by following the questions in the boxes.

If the condition is true (answers yes), go down to the

next box. If the condition is not true (answers no), go

to the box alongside.
Continue checking and answering conditions in each

box until a problem and/or the repair is explained. Use

the Component Checks section as necessary to per-

form system checks.
After any maintenance or repair, the troubleshooting

sequence should be repeated until the procedure ends

with normal system operation.