Middleby Marshall PS200 series User Manual

Page 95

Advertising
background image

94

3. Pilot and Proof of Pilot Flame

Rectification
With standing pilots, heat is

a necessary ingredient for

proper thermocouple opera-

tion. But this is not the case

with IIDS (Intermittent Ignition

Device Systems) when flame

conduction or rectification is

used. To better understand the

principles of flame conduction

and rectification, we must first

understand the structure of a

gas flame. See Figure 66.

Figure 66

Flame structure

Figure 67 - Flame rectification

Figure 68 - Pilot and probe

SECTION 3 - SERVICING COMPONENTS

THE FOLLOWING CONDITIONS WILL HAVE A DIRECT

BEARING ON EVERY IID APPLICATION:
Voltage

The supply voltage to the ignition controls should be

within the following ranges:
•

120VAC controls – 102 to 132VAC

•

24VAC controls – 21 to 26.5VAC

24VAC systems should use transformers that will pro-

vide adequate power under maximum load conditions.

Gas Pressure

Inlet gas pressures

•

Natural gas, Wayne burner - 6-12” W.C. (14.9-29.9 mbar)

•

Propane, Wayne burner - 11½-12” W.C. (28.7-29.9 mbar)

•

Midco burner (all gases) - 6-14” W.C. (14.9-34.9 mbar)

Regulated gas pressures

•

Natural gas, Wayne burner - 3.5” W.C. (8.7 mbar)

•

Propane, Wayne burner - 10” W.C. (24.9 mbar)

•

Midco burner (all gases) - 3-5” W.C. (7.5-12.5 mbar)

Pilot gas pressures

•

Natural gas, Wayne burner - 3½-4” W.C. (8.71-9.95 mbar)

•

Propane, Wayne burner - 8-10” W.C. (19.9-24.9 mbar)

•

Midco burner (all gases) - 5-6” W.C. (12.5-14.9 mbar)

With the proper air-gas ratio to give a blue pilot flame,

three zones exist.
Zone 1: An inner, fuel-rich cone that will not burn be-

cause excess fuel is present.
Zone 2: Around the inner, fuel-rich cone is a blue enve-

lope. In this area is a mixture of vapor from the fuel-rich

inner cone and the secondary, or surrounding, air. This

is where combustion occurs.
Zone 3: Outside the blue envelope is a third zone that

contains an excessive quantity of air and will not burn.
Of concern is the second, or combustion area. This is

where the burning occurs and is the area that is of

prime importance for good flame sensor location.

Flame Rectification

With flame rectification, two probes with different sur-

face areas are exposed to a flame - in this case, the

pilot flame. The probe with the larger surface area at-

tracts more free electrons and, as a result, becomes

the negative probe. Therefore, current is conducted

through the flame from the positive probe to the nega-

tive probe. See Figure 67.
Note also that the AC voltage sine wave has not

changed, but the negative portion of the current sine

wave has been chopped off. This positive portion now

represents a DC current. This is the phenomenon of

flame rectification.
To apply this principle to an IID (Intermittent Ignition

Device - in this case, the pilot/ignitor assembly), a pilot

and flame sensor have been substituted for the two

probes (See Figure 68). After the pilot is ignited, a DC

current flow of 2.0mA (microamps) or more is conducted

through the flame, from the flame sensor (the positive

probe) to the pilot tip (the negative probe). The pilot tip,

acting as the negative probe, completes the circuit to

ground. The IID sensing circuit uses this DC current

flow to energize a relay and open the main burner gas

valve.

Advertising
This manual is related to the following products: