If installing the solar inverter in a switch

box, ensure adequate heat dissipation.

The ambient temperature must not fall

below or exceed –25°C or +40°C.

The solar inverter should not be exposed to

direct solar irradiation, so as to protect it

from unnecessary external heating.

· Protection from damp and foreign bodies

The IP54 high protection class permits instal-

lation both inside and in roofed outdoor

areas, but the solar inverter must not be

exposed to direct rain.

Make sure that the solar inverter cannot be

exposed to foreign bodies (deposits of dust

and dirt).

Requirements on the place of installation

· Mechanical bearing capacity

During installation please bear in mind

that the solar inverter weighs 26 kg. The

installation base must be firm and capable

of continuously bearing the weight.

· Thermal interaction

The installation base must consist of

flame-retardant material (e.g. no wood or

plastic in the base; concrete and brickwork

are suitable), as the heat sink emits tempe-

ratures up to max. 85°C.

A minimum distance of 300 mm must be

maintained above and below the cabinet,

and 150 mm on right and left from other

units, cabinets, ceilings, cable ducts etc..

The solar inverter must be installed verti-

cally, so as not to hinder adequate free

convection.

Several solar inverters must not be instal-

led on top of each other, so as to prevent

reciprocal heating.