96

You must use adequately dimensioned

cable cross-sections in order to avoid a

considerable increase in the grid impedan-

ce between the domestic distribution and

the solar inverter. The terminal range of

the AC terminals is 0.5 to 6 mm2 for rigid

cables and 0.5 to 10 mm2 for flexible

cables. With a high grid impedance, i.e.

with a long line or too small a cross-

section, the voltage increases at the grid

terminal during feed-in.

If the terminal voltage exceeds the per-

missible value, the solar inverter is discon-

nected from the grid.

Carefully perform the following steps:

· Check that there is no voltage before

introducing the supply main into the

unit.

· Lead the 5-core AC cable (outer diame-

ter 9 – 17 mm) through the M25 threa-

ded cable gland.

· Connect cables L1, L2, L3, PE and N to

the relevant circuit board terminal with

the help of a slot-head screwdriver (see

figure below).

· Tighten the M25 screw connection, so

that the cable cannot exert any mechanical

force on the circuit board terminal.