Grid connection

The grid connection of the solar inverter

must have 5 wires (L1, L2, L3, PE, N). Cable

cross-sections of 5 x 4 mm2 are recommen-

ded.

The solar inverter is connected to the

supply grid via the circuit board terminals

inside the unit.

!

As line safety element in the grid feed-in

direction, we recommend a 3 x 25 A auto-

matic cut-out. No consumption units must

be connected to the feed line from the

solar inverter to the automatic cut-out.

The solar inverter only feeds in via termi-

nal L1.

If several solar inverters are operated in

parallel, the feed-in phase L1 of the unit

must be evenly distributed over grid

phases L1, L2 and L3 (see figure below).

L1 N L2 L3 PE

L1 N L2 L3 PE

L1 N L2 L3 PE

L1
L2
L3
N
PE

Three-phase grid connection distributed over three units