The signal is looped through all units. Two

«RS 485+» terminals and two «RS 485-»

terminals are located on each terminal

block. This means that the signal can be led

into the solar inverter at one terminal and

out of the solar inverter at the other termi-

nal. The RS 485 signal is led out of the last

solar inverter in the series into the interface

converter using the following configuration:

«RS 485+» to «DATA+» and «RS 485-» to

«DATA-».

The interface converter generates an

RS 232 signal. It is connected to the PC with

the standard modem cable type D. Jumper

JP400 must be closed at the solar inverter

that is furthest away from the interface

converter. For all other solar inverters it

must be open. An address must be alloca-

ted, to enable identification of the indivi-

dual solar inverters. This is described in

Chapter 2.3 Commissioning, under

«Configuration».

PC

IC

INVER

TER

(2 to 99)

INVER

TER

(1)

PV

PV

MODEM

MODEM

RS 232

RS 232

RS 485

(4) PV system for 2 to 99 solar inverters with interface converter (IC) and modem for

remote inquiry