Sunway NT 2600 User Manual

Page 69

Advertising
background image

Any type of soiling (dust, humidity etc.)

will negatively affect the operation of the

system over the desired period of use.

This applies particularly for the usability

of the seals and crimping of the contacts.

The utmost care must therefore be taken

to work cleanly during installation.

Different circular contacts are used for

different conductor cross-sections for the

TYCO SOLARLOK connectors. The correct

tool insert must be used, depending on

this cross-section. The enclosed TYCO

SOLARLOK connectors are equipped with

circular contacts for a cable cross-section

of 4 mm. The enclosed seals have internal

dimensions of 6 (for cables of 5.3 to 6.2

mm sheath diameter) and 8 mm (for

145

EN

cables of 7.2 to 8.0 mm sheath diameter).

The seal must be matched to the sheath

diameter of the cables used.

The following sequence must be observed

for assembly of TYCO SOLARLOK connec-

tors:

1. Strip the voltage-free cable by 8 mm.

2. Crimp on the circular contact.

3. Push the cable gland, clamping piece

and seal onto the cable.

4. Engage the contact in the connector

housing.

5. Screw on the clamping nut.

6. Tightening torque of the threaded cable

gland is 1.5 Nm.