Sunway NT 2600 User Manual

Page 52

Advertising
background image

128

Fault display

UAC_1

UAC_3

AC under/over-

voltage

Causes

The grid voltage is too low

or too high.

The cable cross-section in

the AC feed line to the solar

inverter is too small.

Your solar system feeds into

a spur line, which is inade-

quately dimensioned.

Remedies

The solar inverter monitors the limits of

the minimum and maximum permissible

3-phase grid voltage. If the values exceed

or fall below these limits (Umin = 184 V,

Umax = 264 V), the solar inverter swit-

ches off and only restarts automatically

when the voltage value has returned

within the limits. The fault cut-out can

be triggered even if the values only

exceed or fall below the limits very

briefly (up to ca. 1 ms).

Ask your electricity board about grid

stability and design.

Check the format of your grid connection

(energy counter) and the grid feed-in

point to your electricity board.